background image

 

Table 1: Installer Configuration Menu (Cont.) 

 

Sets the Minimum Heating/Cooling 
Deadband 
Default: 

2.0

°

F (1.1

°

C) 

See the 

Setting the Heating/Cooling 

Deadband (Deadband)

 section. 

 

Determines how the Fan Activates in 
Response to a call for Heat 
Default: Thermostat Controls Fan 

(On)

See the 

Setting the Fan Control 

(Fan cont)

 section. 

 

Delays Fan Termination at Cycle’s End 
for 60 Seconds 
Default: No Delay 

(Off) 

See the 

Setting the Fan Delay (Fan 

del)

 section. 

 

Sets the Duration for Temporary 
Occupancy Time 
Default: Three Hours 

(3.0 hrs)

 

See the 

Establishing  the Temporary 

Occupancy Time (TOccTime)

 section. 

 

Room Air Sensor Calibration (Offset) 
Default: 

0.0

°

F (0.0

°

C) 

See the 

Room Air Sensor Calibration 

(Cal RS)

 section. 

 

Outdoor Air Sensor Calibration (Offset)
Default: 

0.0

°

F (0.0

°

C) 

See the 

Outdoor Air Sensor 

Calibration (Cal OS)

 section. 

 

Selects the Number of Compressor 
Stages 
Default: Two Stages 
See the 

Enable/Disable Heat Pump 

Stage (HP Stage)

 section. 

 

Disables Heating Operation based on 
Outdoor Air Temperature 
Default: 

120

°

F (49

°

C) 

See the 

Setting the Heating Lockout 

(H lock)

 section.

 

 

Disables Cooling Operation based on 
Outdoor Air Temperature 
Default: 

-40

°

F (-40

°

C) 

See the 

Setting the Cooling Lockout 

(C lock)

 section. 

 

 

 

Sets the Number of Events in 24-Hour 
Period 
Default: Two Events 

(2.0) 

See the 

Selecting the Number of 

Events (2/4event)

 section. 

 

Sets the Auxiliary Contact as Normally 
Open or Normally Closed 
Default: Normally Open 

(N.O.) 

See the 

Configuring the Auxiliary 

Contact (Aux cont)

 section. 

 

Enable/Disable Progressive Recovery 
Default: 

Off 

See the 

Enable/Disable Progressive 

Recovery (Prog Rec)

 section. 

 

Set the High Balance Point 
Default: 

90

°

F (32

°

C) 

See the 

Setting the High Balance Point 

(Hi b.p.)

 section. 

 

Set the Low Balance Point 
Default: 

-12

°

F (-24

°

C) 

See the 

Setting the Low Balance Point 

(Lo b.p)

 section. 

 

Set the Comfort or Economy Mode 
Default: 

Comfort

 

See the 

Selecting Comfort or Economy 

Mode (Comf/eco)

 section. 

 

Sets the Reversing Valve Operation 
Default: 

O

 

See the 

Selecting the Reversing Valve 

Operation (Re valve)

 section. 

 

Sets the Compressor/Auxiliary Heat 
Interlock 
Default: 

Off

 

See the 

Compressor/Auxiliary Interlock 

(Comp/aux)

 section. 

Deadband 
set? Y/N 

2/4event
set? Y/N 

Fan cont 
set? Y/N 

Aux cont
set? Y/N 

Fan del 
set? Y/N 

Prog Rec
set? Y/N 

TOccTime 
set? Y/N 

Hi b.p.
set? Y/N 

Cal RS 
set? Y/N 

Lo b. p.
set? Y/N 

Cal OS 
set? Y/N 

Comf/eco
set? Y/N 

HP Stage 
set? Y/N 

Re valve
set? Y/N 

H lock 
set? Y/N 

Comp/aux
set? Y/N 

 

C lock 
set? Y/N 

6    

T600HPP-2 Programmable Thermostat Installation Instructions 

Summary of Contents for T600HPP-2

Page 1: ...r in a location of average temperature away from direct sunlight radiant heat outside walls behind doors air discharge grills stairwells or outside doors away from steam or water pipes warm air stacks unheated uncooled areas or sources of electrical interference To install the thermostat 1 Remove the security screw on the bottom of the thermostat cover using a Phillips head screwdriver Open the th...

Page 2: ...ks and reinsert on to the new thermostat To wire the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram Figure 5 2 Gently push excess wire back into wall plug the wall hole with fireproof material to prevent drafts from affecting ambient temperature readings and install screw terminal blocks back onto the PCB 3 Reattach the thermosta...

Page 3: ...st stage compressor on a call for heating or cooling Energizes second stage compressor on a call for heating or cooling Energizes fan in accordance with the selected fan mode 24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for auxiliary heat Energizes auxiliary heat Energizes reversing valve configurable to energize valve on a call for heat or call for cooling Con...

Page 4: ...esumes scrolling NO key when you do not desire a parameter change and to advance to the next menu item MENU key to access the Main User Menu or exit the menu UP DOWN arrow keys to adjust values activate a Temporary Setpoint Configuration Key T600_TEC_Config_Key Figure 7 Configuration Key Location Backlit Liquid Crystal Display LCD The T600HPP 2 uses a two line eight character backlit display Low l...

Page 5: ...changing it press the NO key When the thermostat is in the Installer Configuration Menu and left unattended for 45 seconds it reverts to the Status Display Menu Table 1 Installer Configuration Menu Remove the cover and press the CONFIG key from the Status Display Menu to enter the Installer Configuration Menu Configures Digital Input 1 Default No Function None See the Configuring the Digital Input...

Page 6: ...t 40 F 40 C See the Setting the Cooling Lockout C lock section Sets the Number of Events in 24 Hour Period Default Two Events 2 0 See the Selecting the Number of Events 2 4event section Sets the Auxiliary Contact as Normally Open or Normally Closed Default Normally Open N O See the Configuring the Auxiliary Contact Aux cont section Enable Disable Progressive Recovery Default Off See the Enable Dis...

Page 7: ...keys to locate the desired function for the Digital Input 2 Press YES to select the desired function The display now shows the keypad lockout setup prompt See the Enabling Keypad Lockout Lockout section for instructions Enabling Keypad Lockout Lockout The T600HPP 2 has three levels of keypad lockout The levels and degree of lockout are shown in Table 2 To set the keypad lockout level while in the ...

Page 8: ...ns Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establishes the minimum temperature in the cooling setpoint range that can be adjusted from the Main User Menu for both occupied and unoccupied periods The parameter is adjustable from 54 to 100 F 12 to 37 5 C Note When adjusting the temperature holding the keys down changes the temperature by 5 F C increments To set the...

Page 9: ...ing the Heating Cooling Deadband Deadband The heating cooling deadband setting establishes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in the Installer Configuration Menu 1 Answer NO to all prompts until the deadband setpoint prompt appears in the displ...

Page 10: ...ments of 1 F 0 5 C To change the outdoor air sensor calibration offset while in the Installer Configuration Menu 1 Answer NO to all prompts until the outdoor sensor calibration prompt appears in the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The displ...

Page 11: ...ux cont The auxiliary contact is an output that can be used to energize peripheral devices for example lighting equipment exhaust fans and economizers The contact can be configured as normally open or normally closed and toggles with the internal occupied unoccupied schedule or the remote NSB contact on one of the digital inputs if used Table 3 Operation of Auxiliary Contact Configuration Setup Co...

Page 12: ...ature selects how the auxiliary heat is used on heat pump models The selections are Comfort or Economy mode Comfort Mode in heating mode If the heat pump is not able to satisfy the heating setpoint the auxiliary heat is energized to satisfy the same heating setpoint Economy Mode in heating mode If the heat pump is not able to satisfy the heating setpoint the auxiliary heat is energized to satisfy ...

Page 13: ...r Menu by pressing the MENU key during normal thermostat operation The Main User Menu contains the basic operating features of the T600HPP 2 The Main User Menu uses Auto Help Auto Help is displayed automatically in the Main User Menu when there is a pause in programming activity To exit Auto Help continue with the programming selection When the thermostat is in the Main User Menu and is left unatt...

Page 14: ...pt 2 Press YES to resume the programmed schedule The T600HPP 2 thermostat returns to the Status Display Menu Entering Permanent Temperature Setpoints The first prompt appearing in the Main User Menu of the T600HPP 2 thermostat is to set the permanent temperature setpoints Permanent setpoints are stored in the programmed schedule To enter the permanent heating and cooling setpoints for the occupied...

Page 15: ... the default setting Unocc HT set Y N Cooling Mode cool Cooling operation only Heating Mode heat Heating operation only Unocc HT 62 0 F Off Mode off The T600HPP 2 is off However when frost protection is on see the Enabling Frost Protection Frost pr section the thermostat still calls for heat if required F C set Y N Emergency Heat Mode emergenc Forced auxiliary heat operation mode only To set the s...

Page 16: ... Press MENU from the Status Display Menu to enter the Main User Menu Answer NO to all prompts until the schedule set prompt appears in the display Press YES to enter the scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday Use the UP DOWN arrow keys to set the occupied start time Press Y...

Page 17: ...pt appears in the display Press YES to enter the scheduling menu Press YES to set the schedule for Monday or NO to advance to Tuesday Press YES to set the occupied start time for Monday or NO to advance to Tuesday Use the UP DOWN arrow keys to set the first occupied start time Press YES to enter the time Use the UP DOWN arrow keys to set the first unoccupied start time Press YES to enter the time ...

Page 18: ...e day 6 Press YES to choose the time format or NO to access the Main User Menu exit prompt 7 Use the UP DOWN arrow keys to select the desired time format Press YES to enter format 8 Press YES to return to the Status Display Menu or NO to return to the time set menu When the thermostat scrolls through the day and time the new day and time should be displayed and no alarm backlit should be present I...

Page 19: ...Table 9 Optional Accessories Includes Mounting Hardware Description Product Code Number Remote Indoor Temperature Sensor SEN 600 1 Outdoor Air Temperature Sensor SEN 600 2 Duct Mount Temperature Sensor SEN 600 3 Remote Indoor Temperature Sensor with Occupancy Override and LED SEN 600 4 T600HPP 2 Programmable Thermostat Installation Instructions 19 ...

Page 20: ...pment has been tested and found to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interference when this equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accord...

Reviews: