Table 1: Installer Configuration Menu (Cont.)
Sets the Minimum Heating/Cooling
Deadband
Default:
2.0
°
F (1.1
°
C)
See the
Setting the Heating/Cooling
Deadband (Deadband)
section.
Determines how the Fan Activates in
Response to a call for Heat
Default: Thermostat Controls Fan
(On)
See the
Setting the Fan Control
(Fan cont)
section.
Delays Fan Termination at Cycle’s End
for 60 Seconds
Default: No Delay
(Off)
See the
Setting the Fan Delay (Fan
del)
section.
Sets the Duration for Temporary
Occupancy Time
Default: Three Hours
(3.0 hrs)
See the
Establishing the Temporary
Occupancy Time (TOccTime)
section.
Room Air Sensor Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See the
Room Air Sensor Calibration
(Cal RS)
section.
Outdoor Air Sensor Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See the
Outdoor Air Sensor
Calibration (Cal OS)
section.
Selects the Number of Compressor
Stages
Default: Two Stages
See the
Enable/Disable Heat Pump
Stage (HP Stage)
section.
Disables Heating Operation based on
Outdoor Air Temperature
Default:
120
°
F (49
°
C)
See the
Setting the Heating Lockout
(H lock)
section.
Disables Cooling Operation based on
Outdoor Air Temperature
Default:
-40
°
F (-40
°
C)
See the
Setting the Cooling Lockout
(C lock)
section.
Sets the Number of Events in 24-Hour
Period
Default: Two Events
(2.0)
See the
Selecting the Number of
Events (2/4event)
section.
Sets the Auxiliary Contact as Normally
Open or Normally Closed
Default: Normally Open
(N.O.)
See the
Configuring the Auxiliary
Contact (Aux cont)
section.
Enable/Disable Progressive Recovery
Default:
Off
See the
Enable/Disable Progressive
Recovery (Prog Rec)
section.
Set the High Balance Point
Default:
90
°
F (32
°
C)
See the
Setting the High Balance Point
(Hi b.p.)
section.
Set the Low Balance Point
Default:
-12
°
F (-24
°
C)
See the
Setting the Low Balance Point
(Lo b.p)
section.
Set the Comfort or Economy Mode
Default:
Comfort
See the
Selecting Comfort or Economy
Mode (Comf/eco)
section.
Sets the Reversing Valve Operation
Default:
O
See the
Selecting the Reversing Valve
Operation (Re valve)
section.
Sets the Compressor/Auxiliary Heat
Interlock
Default:
Off
See the
Compressor/Auxiliary Interlock
(Comp/aux)
section.
Deadband
set? Y/N
2/4event
set? Y/N
Fan cont
set? Y/N
Aux cont
set? Y/N
Fan del
set? Y/N
Prog Rec
set? Y/N
TOccTime
set? Y/N
Hi b.p.
set? Y/N
Cal RS
set? Y/N
Lo b. p.
set? Y/N
Cal OS
set? Y/N
Comf/eco
set? Y/N
HP Stage
set? Y/N
Re valve
set? Y/N
H lock
set? Y/N
Comp/aux
set? Y/N
C lock
set? Y/N
6
T600HPP-2 Programmable Thermostat Installation Instructions