Configuring the Digital Inputs (DI1 and DI2)
Press the configuration menu access key. The first
prompt is to program Digital Inputs DI1 and DI2.
The digital inputs display an alarm condition when the
input is closed. An alarm message is included on the
scrolling Status Display Menu, and when the message
displays, the backlight momentarily lights up.
Each digital input can be programmed in one of five
conditions:
•
None
– No function is associated with the input.
•
Service
– A Service alarm is displayed.
•
Filter
– A Filter alarm is displayed.
•
RemNSB
– Remote Night Setback (NSB) timer
clock input. The scheduling is set per the digital
input when this option is selected. The time
continues to be displayed, but the menu related to
scheduling is disabled and no longer accessible.
−
Open Contact = Occupied setpoints
−
Closed Contacts = Unoccupied setpoints
•
RemOVR
– Remote override contact. This
disables all override menu functions of the
thermostat. The override function is controlled
manually by a remote, momentarily closed
contact. When configured in this mode, the input
operates in a toggle mode. With this function
enabled, it is now possible to toggle between
unoccupied and occupied setpoints for the amount
of time set by the temporary occupancy time
parameter.
When override is enabled through the digital
inputs, an
Override
message appears in the
Status Display Menu.
To configure the digital inputs while in the Installer
Configuration Menu:
1. The first prompt is to configure the digital inputs.
Press YES to configure Digital Input 1 or NO to
advance to Digital Input 2.
2. Use the UP/DOWN arrow keys to locate the
desired function for the Digital Input 1. Press YES
to select the desired function.
3. Press YES to configure Digital Input 2 or NO to
advance to the keypad lockout setup prompt.
4. Use the UP/DOWN arrow keys to locate the
desired function for the Digital Input 2. Press YES
to select the desired function.
The display now shows the keypad lockout setup
prompt. See the
Enabling Keypad Lockout (Lockout)
section for instructions.
Enabling Keypad Lockout (Lockout)
The T600HPP-2 has three levels of keypad lockout.
The levels and degree of lockout are shown in Table 2.
To set the keypad lockout level while in the Installer
Configuration Menu:
1. Answer NO to all prompts until the keypad lockout
setup prompt appears in the display. Press YES to
enter the keypad lockout menu.
2. Use the UP/DOWN arrow keys to locate the
desired lockout level. Press YES to select the
level.
The display now shows the power delay setup prompt.
See the
Setting the Power-up Delay (Pwr del)
section
for instructions.
Table 2: Keypad Lockout Levels
Level 0
Level 1
Level 2
Resume to
Scheduling
Yes access
Yes access
No access
Temperature
Setpoints
Yes access
No access
No access
System Mode
Setting
Yes access
Yes access
No access
Fan Mode
Setting
Yes access
Yes access
No access
Schedules
Setting
Yes access
No access
No access
Clock Setting
Yes access
Yes access
Yes
access
Permanent
Hold
Yes access
Yes access
No access
Setting the Power-up Delay (Pwr del)
On initial power-up of the T600HPP-2 (or each time
power is removed and reapplied), there is a delay
before any operation is authorized (fan, cooling, and
heating). The delay time is adjustable between 10 and
120 seconds. This parameter can also be used to
sequence the start-up of multiple units in one location.
Note:
When adjusting the time with the UP/DOWN
arrow keys, holding the keys changes the time by
10-second intervals.
To set the delay time while in the Installer
Configuration Menu:
1. Answer NO to all prompts until the power delay
setup prompt appears in the display. Press YES to
enter the power delay setup menu.
2. Use the UP/DOWN arrow keys to adjust the
power-up delay setting. Press YES to store the
setting.
T600HPP-2 Programmable Thermostat Installation Instructions