Programming Overview
There are three menus used to view, program, and
configure the T600HPP-2 thermostat: the Status
Display, Main User, and Installer Configuration Menus.
The
Status Display Menu
is displayed during normal
thermostat operation. The menu continually scrolls
through the following parameters.
•
Room Temperature
•
Day and Time
•
System Mode
•
Schedule Status (Occupied/Unoccupied)
•
Outdoor Temperature (providing sensor is
connected and functional)
•
Applicable Alarms (the backlight lights up as an
alarm condition is displayed)
To temporarily stop the scrolling, press the
YES/SCROLL key.
The
Main User Menu
is used to access and change
the thermostat’s basic operating parameters. Access
the menu by pressing the MENU key during normal
thermostat operation.
The
Installer Configuration Menu
is used to set up
the thermostat for application specific operation.
Access the menu by removing the front cover and
pressing the configuration key, labeled CONFIG
(Figure 7).
Configuring the T600HPP-2
The T600HPP-2 ships from the factory with default
settings for all configurable parameters. The default
settings are shown in Table 1. To reconfigure the
parameters, follow the steps in this section for the
corresponding parameters. To set up the parameters,
access the Installer Configuration Menu. Access the
Installer Configuration Menu by removing the front
cover and pressing the configuration key (Figure 7).
Exit the Installer Configuration Menu any time by
pressing the MENU key and, at the exit prompt,
pressing the YES key. To pass over a parameter
without changing it, press the NO key.
When the thermostat is in the Installer Configuration
Menu and left unattended for 45 seconds, it reverts to
the Status Display Menu.
Table 1: Installer Configuration Menu
Remove the cover and press the
CONFIG key from the Status Display
Menu to enter the Installer
Configuration Menu.
Configures Digital Input 1
Default: No Function
(None)
See the
Configuring the Digital Inputs
(DI1 and DI2)
section.
Configures Digital Input 2
Default: No Function
(None)
See the
Configuring the Digital Inputs
(DI1 and DI2)
section.
Sets Keypad Lockout Level
Default: No Lockout
(0)
See the
Enabling Keypad Lockout
(Lockout)
section.
Sets Power-up Delay
Default: Ten Seconds
(10.0 sec)
See the
Setting the Power-up Delay
(Pwr del)
section.
Enables/Disables Frost Protection
Default: Disabled
(Off)
See the
Enabling Frost Protection
(Frost pr)
section.
Sets the Maximum Heating Setpoint
Default:
90.0
°
F (32.0
°
C)
See the
Setting the Maximum Heating
Setpoint (Heat max)
section.
Sets the Minimum Cooling Setpoint
Default:
54.0
°
F (12.0
°
C)
See the
Setting the Minimum Cooling
Setpoint (Cool min)
section.
Sets the Anti-Short Cycle Timer
Default: Two Minutes
(2.0 min)
See the
Setting the Anti-Short Cycle
Timer (Anticycl).
Sets the Maximum Heating Cycles per
Hour (Auxiliary Heating)
Default: Four
(4.0)
See the
Setting the Maximum Heating
Cycles per Hour (Heat cph)
section.
Sets the Maximum Cooling Cycles per
Hour (Compressor Cycles)
Default: Four
(4.0)
See the
Setting the Maximum Cooling
Cycles per Hour (Cool cph)
section.
Continued on the next page . . .
RoomTemp
75.0
°
F
DI1
set? Y/N
DI2
set? Y/N
Lockout
set? Y/N
Pwr del
set? Y/N
Frost pr
set? Y/N
Heat max
set? Y/N
Cool min
set? Y/N
Anticycl
set? Y/N
Heat cph
set? Y/N
Cool cph
set? Y/N
T600HPP-2 Programmable Thermostat Installation Instructions