ositive temperature cold room

Defrost functions

Defrost is initiated and terminated by a timer. The
user sets the interval between successive cycles and
its duration.

During the defrost cycle, the display can show
either the last measurement before this cycle or
the setpoint. You can also delay the normal
display function after the defrost cycle has
ended.

Manual defrost is possible by pushing a key on the
controller keypad.

Fan management functions

You can choose whether the fan is to be run in
parallel with the compressor or whether it should
remain constantly ON. In this case the fan will be
ON during defrost. This will decrease defrosting
duration.

Pump down selection

A selector is available to choose between the start
stop strategy for the compressor.

Condensing fan

On the 3-phase models, two terminals are
available to field connect a condensing fan.

Digital input functions

All defrost controllers are equipped with a digital
input performing the following functions:

 

Shut-OFF: If the contact is open for a preset

time, all outputs are de-energised and an
alarm message is displayed.

 

External alarm: Display shows AL, the Alarm

output is switched ON, all other functions will
perform as normal

 

Door open: In this case the High alarm will

be disabled, other functions will perform as
normal.

Note:

A detailed list of available parameters and their
description can be found at the end of this
documentation.

Positive Temperature Cold Room Cabinet

Selection table:

Item code

Power supply

Compressor

Evap. Fan

Cond.

Fan

Cabinet

size

Shipping

weight

V ac

Φ

Φ

Φ

Φ

Power

AC-3

Amps

Amps

Amps

modules

Kg

CR-PS037-1

230

1

0,37 kW

5

1,6

-

12

2,2

CR-PS075-1

230

1

0,75 kW

8

1,6

-

12

2,2

CR-PS110-1

230

1

1,1 kW

10

3,2

-

12

2,2

CR-PS150-1

230

1

1,5 kW

12

4,8

-

12

2,2

CR-PT150-1

400

3

1,5 kW

3,5

3,2

3

18

3,2

CR-PT250-1

400

3

2,5 kW

5,7

3,2

3

18

3,2

CR-PT400-1

400

3

4,0 kW

8,5

4,8

3

18

3,2

CR-PT550-1

400

3

5,5 kW

11,5

4,8

3

18

3,2

CR-PT750-1

400

3

7,5 kW

15,5

4,8

3

18

3,2

Fan and
compressor
switched in parallel

Continuous
fan

Solenoid valve and
compressor
switched in parallel

Pump down

4

CR1

Catalogue Section 9

© 2000 Johnson Controls, Inc.

Summary of Contents for CR-NDT150-1

Page 1: ...modules back models Features and Benefits Power rating from 0 37 to 1 5 kW in single phase 1 5 to 7 5 kW in three phases Cover most of standard applications Standard DIN rail components Easy maintena...

Page 2: ...it features a high protection and an appropriate magneto thermal characteristic in function of the application Positive temperature applications Mainly inductive loads Curve D Negative temperature ap...

Page 3: ...al rules These controllers are designed for use as an operating control When an operating control failure would result in personal injury or loss of property it is the responsibility of the installer...

Page 4: ...following functions Shut OFF If the contact is open for a preset time all outputs are de energised and an alarm message is displayed External alarm Display shows AL the Alarm output is switched ON al...

Page 5: ...t pum p down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR12DR230 B1 A D A N 13 7 4 N N N N 4 1 3N 2 4N Alarm 230V 0 5 A 8T4 7L4 21 22 3 Fan Compressor Comp...

Page 6: ...temperature has dropped below a user settable temperature Condensing fan or door frame heater On the 3 phase models two terminals are available to field connect a condensing fan or a door frame heate...

Page 7: ...p down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR15DR230 10 11 B1 A D A B2 A N 13 7 4 N N N N 4 1 3N 2 4N Alarm 230V 0 5 A 8T4 7L4 21 22 N 20 3 Compress...

Page 8: ...g diagram Valve Pum p down Defrost 230 V 3 reaker 1P N Circuit B Circuit 400 V Breaker 3 Contactor Fan 230 Volts A99 Contact pump down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 C...

Page 9: ...1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR15DR230 10 11 B1 A D A B2 A N 13 7 4 N N N N 4 Alarm 230V 0 5 A 8T4 7L4 21 22 Pressure switch HP BP 3 1L1 3L2 5L3...

Page 10: ...room temperature exceeds 4 6 10 C for a time greater than parameter At the alarm is activated when temperature drops below 4 6 2 8 C the alarm is reset At Alarm time delay Delay between the detection...

Page 11: ...digital input opening and the enabling of the function selected through parameter iF FF Fan operating function 0 fan runs in parallel to the compressor 1 fan is always ON Note in both cases the fan is...

Page 12: ...Max defrost duration 0 to 99 min 40 dC Dripping time 0 to 99 min 5 dU First defrost after power on OFF 0 to 99 min OF dP Display during defrost 0 Last value before defrost 1 Set point 0 dr Delay disp...

Page 13: ...er s documentation in this case ABB Characteristic of the circuit breaker for motor three phase models only Item Control range Interruption capacity against short circuit 380 400 Vac Ics kA CR PT150 1...

Page 14: ...que Circuit breakers S254 Cxx series Circuit breaker for 3ph defrost see relative amperage value in the wiring diagram ABB Elettrocondoture S271 Na xxx 1ph N circuit breaker for digital controller see...

Page 15: ...Notes CR1 15 2010 Johnson Controls Inc Catalogue Section 9...

Page 16: ...mps 230 V ac Dimensions H x W x D 12 Modules 18 Modules 24 Modules 36 Modules 275 x 220 x 140 380 x 220 x 140 275 x 370 x 140 380 x 370 x 140 Directives EN 60439 1 Tested Type Appliance TTA The perfor...

Page 17: ...isfonctionnement d un appareil de r gulation peut entrainer des blessures au personnel ou une perte d exploitation la responsabilit en incombe l installateur Celui ci doit pr voir des quipements ou de...

Page 18: ...eme die bei Ausfall oder St rung der Steuerung eine Warn oder Schutzfunktion haben in die Steuerung integriert und als Teil des Regelsystems gewartet werden Nota Estos controles est n dise ados para s...

Page 19: ...et installat rens ansvar at installere udstyr eller systemer der kan beskytte mod eller advare om styringsfejl Huomaa N m s timet on tarkoitettu k ytett v ksi vain k ytt s timin Asentaja on vastuussa...

Page 20: ...atorsch tz Motorschutzschalter Verdampfer Ventilatorschutzschalter Abtauschutzschalter 4 polig Reglerschutzschalter Hauptsch tz NEDERLANDS Regelaar Compressor relais Ontdooi relais Verdamper Ventilato...

Reviews: