Johnson Controls CR-NDT150-1 Manual Download Page 11

dU

First defrost cycle after power-on:

This parameter allows to delay a defrost cycle,
after power-up. This will prevent a cycle from
occurring before the cold room has reached its
operation temperature.
When set to ‘OFF’, the first defrost will occur
after a complete defrost interval (parameter di)

dP 

Display during defrosts:

You can select what to display during the defrost
cycle. This is meant to avoid misleading users
during the defrost cycle.
0 =  last measured value before defrost cycle
1 =  setpoint

dr

Delay displayed temperature after defrost

During defrost cycles the ambient temperature is
not displayed (see parameter dP). The actual
temperature returns to display when its value
reaches the setpoint value or, in any case, after
the time defined by this parameter.

iF

Digital input function:

The digital input (normally closed) can be
configured according to the plant requirements:

0=  the DI is not connected

1=  If the contact is open for a time longer than that

set through parameter id, the plant is switched
OFF and an alarm message is displayed; this
can be used for condenser alarm...

2=  Alarm function: in this case an alarm message

is displayed and the alarm digital output is
switched ON

3=  Open door in the cold room. When the contact

is open, the fan is switched OFF (when
applicable) and if the contact is open for more
than the time set through parameter id an alarm
message is displayed and the alarm output is
switched ON. High and low alarms are disabled.

id

Digital input time delay:

Time between the detection of the digital input
opening and the enabling of the function
selected through parameter iF.

FF

Fan operating function:

0=  fan runs in parallel to the compressor
1=  fan is always ON

Note: in both cases, the fan is switched OFF
during the defrost cycle.

Fd

Fan start-up delay after defrost end:

This parameter is a safety function, the fan is
activated after this time even if the temperature
set through parameter Fr has not been reached

Fr

Fan start temperature after defrosts end:

Evaporator sensor temperature at which the fan
is switched ON, after defrost cycle,
Note: in any case the fan is switched ON after
the time set through parameter Fd.

SF

Thermostat operating function when sensor
failure:

This defines the cycle of the thermostat output in
case of failure
0 = Compressor ON
1 = Compressor OFF
2 = Automatic
In this mode, the controller will calculate the
average time the compressor was ON for the
last 4 cycles, and the compressor will run
accordingly. If a deep freezing cycle or a defrost
cycle occurred, they will not be taken into
account nor will the first cycle afterwards.

So

Offset thermostat sensor:

This value is added to or subtracted from the
measured value to compensate for possible field
measurement offset errors. To compensate for
extra long copper cabling use the following
formula:

5

length

1

area

= −

×

×

K

0 0 0

C om p ens ation

Where:
length = length of the cable in meters
area = section of the cable in square millimetres
and compensate for the calculated value

Un

Temperature units:

0 = Celsius degrees,
1 = Fahrenheit degrees.

PU

Display updating time delay:

The temperature value displayed will be
refreshed with this defined period. It will not
affect the control performance.

CR1

11

© 2010 Johnson Controls, Inc. 

Catalogue Section 9

Summary of Contents for CR-NDT150-1

Page 1: ...modules back models Features and Benefits Power rating from 0 37 to 1 5 kW in single phase 1 5 to 7 5 kW in three phases Cover most of standard applications Standard DIN rail components Easy maintena...

Page 2: ...it features a high protection and an appropriate magneto thermal characteristic in function of the application Positive temperature applications Mainly inductive loads Curve D Negative temperature ap...

Page 3: ...al rules These controllers are designed for use as an operating control When an operating control failure would result in personal injury or loss of property it is the responsibility of the installer...

Page 4: ...following functions Shut OFF If the contact is open for a preset time all outputs are de energised and an alarm message is displayed External alarm Display shows AL the Alarm output is switched ON al...

Page 5: ...t pum p down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR12DR230 B1 A D A N 13 7 4 N N N N 4 1 3N 2 4N Alarm 230V 0 5 A 8T4 7L4 21 22 3 Fan Compressor Comp...

Page 6: ...temperature has dropped below a user settable temperature Condensing fan or door frame heater On the 3 phase models two terminals are available to field connect a condensing fan or a door frame heate...

Page 7: ...p down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR15DR230 10 11 B1 A D A B2 A N 13 7 4 N N N N 4 1 3N 2 4N Alarm 230V 0 5 A 8T4 7L4 21 22 N 20 3 Compress...

Page 8: ...g diagram Valve Pum p down Defrost 230 V 3 reaker 1P N Circuit B Circuit 400 V Breaker 3 Contactor Fan 230 Volts A99 Contact pump down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 C...

Page 9: ...1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR15DR230 10 11 B1 A D A B2 A N 13 7 4 N N N N 4 Alarm 230V 0 5 A 8T4 7L4 21 22 Pressure switch HP BP 3 1L1 3L2 5L3...

Page 10: ...room temperature exceeds 4 6 10 C for a time greater than parameter At the alarm is activated when temperature drops below 4 6 2 8 C the alarm is reset At Alarm time delay Delay between the detection...

Page 11: ...digital input opening and the enabling of the function selected through parameter iF FF Fan operating function 0 fan runs in parallel to the compressor 1 fan is always ON Note in both cases the fan is...

Page 12: ...Max defrost duration 0 to 99 min 40 dC Dripping time 0 to 99 min 5 dU First defrost after power on OFF 0 to 99 min OF dP Display during defrost 0 Last value before defrost 1 Set point 0 dr Delay disp...

Page 13: ...er s documentation in this case ABB Characteristic of the circuit breaker for motor three phase models only Item Control range Interruption capacity against short circuit 380 400 Vac Ics kA CR PT150 1...

Page 14: ...que Circuit breakers S254 Cxx series Circuit breaker for 3ph defrost see relative amperage value in the wiring diagram ABB Elettrocondoture S271 Na xxx 1ph N circuit breaker for digital controller see...

Page 15: ...Notes CR1 15 2010 Johnson Controls Inc Catalogue Section 9...

Page 16: ...mps 230 V ac Dimensions H x W x D 12 Modules 18 Modules 24 Modules 36 Modules 275 x 220 x 140 380 x 220 x 140 275 x 370 x 140 380 x 370 x 140 Directives EN 60439 1 Tested Type Appliance TTA The perfor...

Page 17: ...isfonctionnement d un appareil de r gulation peut entrainer des blessures au personnel ou une perte d exploitation la responsabilit en incombe l installateur Celui ci doit pr voir des quipements ou de...

Page 18: ...eme die bei Ausfall oder St rung der Steuerung eine Warn oder Schutzfunktion haben in die Steuerung integriert und als Teil des Regelsystems gewartet werden Nota Estos controles est n dise ados para s...

Page 19: ...et installat rens ansvar at installere udstyr eller systemer der kan beskytte mod eller advare om styringsfejl Huomaa N m s timet on tarkoitettu k ytett v ksi vain k ytt s timin Asentaja on vastuussa...

Page 20: ...atorsch tz Motorschutzschalter Verdampfer Ventilatorschutzschalter Abtauschutzschalter 4 polig Reglerschutzschalter Hauptsch tz NEDERLANDS Regelaar Compressor relais Ontdooi relais Verdamper Ventilato...

Reviews: