Johnson Controls CR-NDT150-1 Manual Download Page 10

D

escription of each parameter

Setpoint :

is defined as the relay cut OFF.

Hy Hysteresis

This is the difference between the temperature
at which the compressor output is switched OFF
and the temperature at which the output is
switched ON. This is an absolute value, related
to the setpoint.

Example: 
Cooling Setpoint = 4 ºC
Differential = 2 K.
The compressor is switched
ON when the temperature
goes over 6 ºC, and is turned
OFF when the temperature
decreases to 4 ºC.

LL/HL Lower & Higher setpoint limit

The setpoint value cannot be adjusted outside
the limits defined by these parameters, to avoid
improper setpoint setting by the user.

CC 

Anti short cycle protection

This parameter prevents the compressor from
being turned ON / OFF too often. The value that
you set is the minimum time between two
subsequent switches ON of the output.

Cooling demand

Comp. output

Anti cycle timer

Co 

Deep freezing time

This is the time for which the compressor is
forced ON when pressing the deep freezing
cycle key from the faceplate.

AH 

High temperature alarm:

High temperature alarm value relative to
setpoint. If your set point is at 4ºC and you want
an alarm 5 K above setpoint, it will be triggered
at 9ºC.

AL 

Low temperature alarm:

Low temperature alarm value relative to setpoint.
If your set point is at 4ºC and you want an alarm
3 K below setpoint, it will be triggered at 1ºC.

Ad Alarm 

differential:

Useful to avoid alarm oscillations.
For example:
Setpoint = 4ºC,
Max. Temperature alarm = 6 K,
Alarm differential = 2 K.
In this case, when the cold room temperature
exceeds 4+6 = 10ºC for a time greater than
parameter At the alarm is activated; when
temperature drops below 4+6-2 = 8ºC the alarm
is reset

At 

Alarm time delay:

Delay between the detection of the temperature
alarm and the activation of the alarm sequences.
This is useful to prevent temporary conditions
from causing an alarm. Furthermore, the
controller automatically ignores the temperature
alarm condition in the following cases:

for 20 minutes after the power-ON

-

 

during defrost and for 20 minutes after the
defrost-end.

dF Defrost 

function:

Select the type of your installation and the way
defrost is performed
0 = Electrical defrost (Compressor OFF)
1 = Hot gas defrost (Compressor ON)

dE 

Defrost end function:

Select the defrost termination type:
0 = timer based, set with parameter dd
In this case the evaporator sensor is not
required and the fan will restart base on time.
1 = temperature based, set with parameter dt
Note: in any case defrost ends after the time set
on parameter dd.

dt

Defrost termination temperature:

Used only when parameter dE =1. When the
evaporator temperature reaches this value,
defrost automatically ends.

di

Defrost interval time:

This is the time between two subsequent defrost
cycles. This timer will initiate every defrost cycle.

dd

Maximum defrost duration:

If defrost end by time has been selected
(parameter dE=1) defrost cycle will stop after this
time, even if the end temperature has not
reached parameter dt.
When defrost interval time is 1 hour, the
maximum duration is limited to 40 min.

dC

Dripping time:

After defrost is terminated, the compressor is
stopped to allow the evaporator to drip.

Hysteresis

Cooling Setpoint

T ° C

10

CR1

Catalogue Section 9

© 2000 Johnson Controls, Inc.

Summary of Contents for CR-NDT150-1

Page 1: ...modules back models Features and Benefits Power rating from 0 37 to 1 5 kW in single phase 1 5 to 7 5 kW in three phases Cover most of standard applications Standard DIN rail components Easy maintena...

Page 2: ...it features a high protection and an appropriate magneto thermal characteristic in function of the application Positive temperature applications Mainly inductive loads Curve D Negative temperature ap...

Page 3: ...al rules These controllers are designed for use as an operating control When an operating control failure would result in personal injury or loss of property it is the responsibility of the installer...

Page 4: ...following functions Shut OFF If the contact is open for a preset time all outputs are de energised and an alarm message is displayed External alarm Display shows AL the Alarm output is switched ON al...

Page 5: ...t pum p down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR12DR230 B1 A D A N 13 7 4 N N N N 4 1 3N 2 4N Alarm 230V 0 5 A 8T4 7L4 21 22 3 Fan Compressor Comp...

Page 6: ...temperature has dropped below a user settable temperature Condensing fan or door frame heater On the 3 phase models two terminals are available to field connect a condensing fan or a door frame heate...

Page 7: ...p down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR15DR230 10 11 B1 A D A B2 A N 13 7 4 N N N N 4 1 3N 2 4N Alarm 230V 0 5 A 8T4 7L4 21 22 N 20 3 Compress...

Page 8: ...g diagram Valve Pum p down Defrost 230 V 3 reaker 1P N Circuit B Circuit 400 V Breaker 3 Contactor Fan 230 Volts A99 Contact pump down A99 1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 C...

Page 9: ...1L1 3L2 5L3 2T1 4T2 6T3 I I I A1 1L1 3L2 5L3 2T1 4T2 6T3 A2 Compressor 3 400 Volts MR15DR230 10 11 B1 A D A B2 A N 13 7 4 N N N N 4 Alarm 230V 0 5 A 8T4 7L4 21 22 Pressure switch HP BP 3 1L1 3L2 5L3...

Page 10: ...room temperature exceeds 4 6 10 C for a time greater than parameter At the alarm is activated when temperature drops below 4 6 2 8 C the alarm is reset At Alarm time delay Delay between the detection...

Page 11: ...digital input opening and the enabling of the function selected through parameter iF FF Fan operating function 0 fan runs in parallel to the compressor 1 fan is always ON Note in both cases the fan is...

Page 12: ...Max defrost duration 0 to 99 min 40 dC Dripping time 0 to 99 min 5 dU First defrost after power on OFF 0 to 99 min OF dP Display during defrost 0 Last value before defrost 1 Set point 0 dr Delay disp...

Page 13: ...er s documentation in this case ABB Characteristic of the circuit breaker for motor three phase models only Item Control range Interruption capacity against short circuit 380 400 Vac Ics kA CR PT150 1...

Page 14: ...que Circuit breakers S254 Cxx series Circuit breaker for 3ph defrost see relative amperage value in the wiring diagram ABB Elettrocondoture S271 Na xxx 1ph N circuit breaker for digital controller see...

Page 15: ...Notes CR1 15 2010 Johnson Controls Inc Catalogue Section 9...

Page 16: ...mps 230 V ac Dimensions H x W x D 12 Modules 18 Modules 24 Modules 36 Modules 275 x 220 x 140 380 x 220 x 140 275 x 370 x 140 380 x 370 x 140 Directives EN 60439 1 Tested Type Appliance TTA The perfor...

Page 17: ...isfonctionnement d un appareil de r gulation peut entrainer des blessures au personnel ou une perte d exploitation la responsabilit en incombe l installateur Celui ci doit pr voir des quipements ou de...

Page 18: ...eme die bei Ausfall oder St rung der Steuerung eine Warn oder Schutzfunktion haben in die Steuerung integriert und als Teil des Regelsystems gewartet werden Nota Estos controles est n dise ados para s...

Page 19: ...et installat rens ansvar at installere udstyr eller systemer der kan beskytte mod eller advare om styringsfejl Huomaa N m s timet on tarkoitettu k ytett v ksi vain k ytt s timin Asentaja on vastuussa...

Page 20: ...atorsch tz Motorschutzschalter Verdampfer Ventilatorschutzschalter Abtauschutzschalter 4 polig Reglerschutzschalter Hauptsch tz NEDERLANDS Regelaar Compressor relais Ontdooi relais Verdamper Ventilato...

Reviews: