background image

3

18

4.

DUCT SYSTEM

(See British Design Manual - Gas fired Warm Air Heating)

4.1

RETURN AIR

4.1.1

All return air shall be POSITIVELY ducted from outside the compartment to the top of the unit via a return air duct or, if
appropriate, using a Side Return Air Kit SR50, and mechanically secured. It is recommended that the return air duct be
not routed directly from the main living area, but from a convenient central area serving the remainder of the dwelling.

4.1.2

The return air system should be constructed of fire-resistant material. The flue shall not be run through an area serving
as a return air path. It is extremely important that the correct size of return air grilles and ducting is used. For heaters on
maximum output the return air duct size should not be less than the equivalent of 300mm x 250mm (12" x 10"). If flexible
duct is used the duct diameter should not be less than 350mm (14") dia. The return air grille should have a free area of
not less than 1266cm

2

 (196in

2

).

4.1.3

An adequate and unobstructed return air path is essential from areas not served by a directly ducted return and to
which warm air is delivered. All such rooms should be fitted with relief grilles which have a free area of 0.0088m

2

/kW

(1in

2

/250Btu/h) of heat supplied to the room. The only exceptions are kitchens, bathrooms and WC.’s.

4.1.4

The return air duct should allow for ease of removal for access to the flue.

4.1.5

All duct work in the room or internal space in which the heater is installed shall be mechanically secured, and sealed
with ducting tape.

4.2

WARM DELIVERED AIR

4.2.1

All duct work, including riser ducts, should be fully insulated with 50mm (2in) fibreglass or similar. If short extended
duct runs are taken below floor level these should be similarly insulated, and in addition wrapped with a sound vapour
proof barrier, and protected from crushing.

4.2.2

The duct system should be carefully designed (as given in the guidelines in the British System Design Manual) to suit
the needs of its specific heating requirements and building layout. The type of duct system, (i.e. radial/extended
plenum/stepped) should be installed using the least number of fittings to minimise airflow resistance. The base duct,
which equalises the air pressure to supply ducts, shall be constructed to support the weight of the heater, which shall
be secured to the plenum with screws on at least two sides, and sealed using self-adhesive foam strip, ducting tape or
sealing compound. All ducting and blanking plates shall be mechanically secured and sealed.

5.

INSTALLATION REQUIREMENTS

5.1  

FLUES 

(see British Standards BS 5440 Pt. 1 Flues)

5.1.1

All joints shall be soundly sealed.

5.1.2

The flue should be kept as short and warm as possible.

5.1.3

Sufficient support brackets shall be installed to bear the weight of the total flue system.

5.1.4

The spigot connection of the heater draught diverter will accept internally the spigot end of a non-asbestos flueto BS
567 or twin wall metal flue to BS 715 of nominal 100mm (4in) diameter.

5.1.5

A split collar should be fitted to provide for flue maintenance or inspection.

5.1.6

The flue shall be in accordance with the Building Regulations and British Gas Materials and  Installations specification
3rd edition) with regard to clearance and shielding from combustible materials.

5.1.7

All materials shall be in accordance with Building Regulations requirements.

5.1.8

The flue should run as vertically as possible. Horizontal runs should be avoided if at all possible and any directional

Ventilated from inside
building.

Low level grille

448cm

2

 (69in

2

)

High level grille

224cm

2

 (34in

2

)

Ventilated from

outside building.

Low level grille

224cm

2

 (34in

2

)

High level grille

112cm

2

 (14

2

)

Table 1

Minimum Effective Areas

WARM AIR UNIT

HOT WATER GENERATOR

CONTROLS

 to comply with the Building Regulations, each section must have a tick on one or other of the boxes

FOR WARM AIR HEATERS ONLY

Has the system been balanced in accordance with the heater manufacturer’s instructions?

YES

NO

Was an anemometer used?

YES

NO

Have balancing dampers been fitted?

YES

NO

FOR WARM AIR HEATING: MEASURE AND RECORD

Burner operating pressure

Mbar

Heat input

KW

Temperature differential between return air inlet and nearest outlet

o

C

FOR HOT WATER GENERATORS: MEASURE AND RECORD

Burner operating pressure

Mbar

Heat input

KW

Water flow temperature

o

C

FOR ALL PRODUCTS

Does the heating & hot water system comply with the appropriate building regulations?

YES

NO

Has the appliance and associated controls been installed & commissioned in accordance with manufacturer’s instructions?

YES

NO

Have you demonstrated the operation of the appliance & system controls to the customer?

YES

NO

Have you left all the manufacturer’s literature with the customer

YES

NO

Competent  person’s  signature  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Customer’s  Signature  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

(To confirm demonstration of equipment & receipt of appliance instructions)

COMMISSIONING ENGINEER’S DETAILS

Name  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Commissioning  Date  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Address  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Tel  No  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CORGI  REGISTRATION  No  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CORGI  ID  SERIAL  No  . . . . . . . . . . . . . . . . . . . . . . . . . . .

BENCHMARK Number

WARM AIR HEATER AND CIRCULATOR
COMMISSIONING CHECKLIST

REQUIREMENT

1. Time & temp control to heating

2. Time & temp control to hot water

3. Heating zone valves

4. Thermostatic Radiator Valves

5. Boiler interlock

MEASURES PROVIDED

Room stat & integral timer

Cylinder stat & Integral timer

Fitted

Not Required

Fitted

Not Required

Provided

Not Required

APPLIANCE  SERIAL  NUMBER:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NOTIFICATION  No:  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

APPLIANCE  SERIAL  NUMBER:  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . NOTIFICATION  No:  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

169cm

 (26.2in

)

169cm

 (26.2in

)

337cm

 (52.3in

)

85cm

 (13.1in

)

Summary of Contents for HI-SPEC J50P

Page 1: ...4 739 BOS00105 Overheat limitControl 1 Honeywell L4069C 6 393 412 BOS02237 Multifunctionalcontrol 1 Honeywell V8600D 7 232 903 BOS02061 Sealing ring for item 6 2 8 BOS02397 2 Pilot assembly 1 9 E01 08...

Page 2: ...her insulation is needed 2 9 For Slot Fix applications see instructions packed with the Slot Fix Kit it is important to ensure that the draught diverter relief is maintained on both sides of the appli...

Page 3: ...oundly sealed 5 1 2 The flue should be kept as short and warm as possible 5 1 3 Sufficient support brackets shall be installed to bear the weight of the total flue system 5 1 4 The spigot connection o...

Page 4: ...ssessed in terms of equivalent vertical height details are given in 5 1 11 For air heaters the minimum equivalent vertical height is 1 metre The installer must make a judgement based on his knowledge...

Page 5: ...e 3 contains the appropriate inlet and outlet flue resistances the flue is likely to be satisfactory if its equivalent height exceeds 1m d WorkedCalculationExample A warm air unit with a 100 mm diamet...

Page 6: ...ectified and the test satisfactorily completed 5 2 ELECTRICAL 5 2 1 Mains a The heater is supplied with mains cable PVC sheathed heat resisting to 85o C 3 core Brown Blue Green Yellow 6A 0 75mm2 conne...

Page 7: ...following locations i In a room where temperature is greatly affected by the sun or any other heat source e g radiant fire wall light fittings or TV set ii Near an outside door or windows or on an out...

Page 8: ...TAPPING1 150V TAPPING2 170V TAPPING3 190V TAPPING4 210V TAPPING5 230V 8 9 6 Disconnect 2 x TTB connections 8 9 7 Disconnect the Multifunctional Control connections 8 9 8 Release 4 x 4mm screws securi...

Page 9: ...e Electrical Assembly cable clamp 8 9 5 Disconnect the following a Disconnect 230V connections L N E from Fan Assembly b 230V mains L N and E from connection block terminals 1 and 3 and earth stud res...

Page 10: ...ar introduce a light source into the heat exchanger burner aperture and upper access port and again examine the heat exchanger for signs of cracks or holes particularly around welded joints whilst aga...

Page 11: ...ar introduce a light source into the heat exchanger burner aperture and upper access port and again examine the heat exchanger for signs of cracks or holes particularly around welded joints whilst aga...

Page 12: ...e Electrical Assembly cable clamp 8 9 5 Disconnect the following a Disconnect 230V connections L N E from Fan Assembly b 230V mains L N and E from connection block terminals 1 and 3 and earth stud res...

Page 13: ...TAPPING1 150V TAPPING2 170V TAPPING3 190V TAPPING4 210V TAPPING5 230V 8 9 6 Disconnect 2 x TTB connections 8 9 7 Disconnect the Multifunctional Control connections 8 9 8 Release 4 x 4mm screws securi...

Page 14: ...following locations i In a room where temperature is greatly affected by the sun or any other heat source e g radiant fire wall light fittings or TV set ii Near an outside door or windows or on an out...

Page 15: ...ectified and the test satisfactorily completed 5 2 ELECTRICAL 5 2 1 Mains a The heater is supplied with mains cable PVC sheathed heat resisting to 85o C 3 core Brown Blue Green Yellow 6A 0 75mm2 conne...

Page 16: ...e 3 contains the appropriate inlet and outlet flue resistances the flue is likely to be satisfactory if its equivalent height exceeds 1m d WorkedCalculationExample A warm air unit with a 100 mm diamet...

Page 17: ...ssessed in terms of equivalent vertical height details are given in 5 1 11 For air heaters the minimum equivalent vertical height is 1 metre The installer must make a judgement based on his knowledge...

Page 18: ...oundly sealed 5 1 2 The flue should be kept as short and warm as possible 5 1 3 Sufficient support brackets shall be installed to bear the weight of the total flue system 5 1 4 The spigot connection o...

Page 19: ...her insulation is needed 2 9 For Slot Fix applications see instructions packed with the Slot Fix Kit it is important to ensure that the draught diverter relief is maintained on both sides of the appli...

Page 20: ...4 739 BOS00105 Overheat limitControl 1 Honeywell L4069C 6 393 412 BOS02237 Multifunctionalcontrol 1 Honeywell V8600D 7 232 903 BOS02061 Sealing ring for item 6 2 8 BOS02397 2 Pilot assembly 1 9 E01 08...

Reviews: