background image

ZZ1027/3

7

14

SYMPTOM

POSSIBLE CAUSE

REMEDY

a. Pilot will not light.

i.

No gas supply to heater.

Check for gas at inlet pressure test
point on Multifunctional Control.

ii.

Gas supply pipe not purged.

Purge gas supply pipe in accordance
with BS 6891.

iii

Pilot orifice restricted.

Clear pilot orifice or replace pilot injector.

iv.

Piezo system faulty.

Check igniter, lead, and electrode.

v.

Excessive  gas  supply  pressure.

Check that mains gas pressure is 37mbar,
and reduce if necessary.

b. Pilot lights but goes

i.

Connection between thermo-

Check connection is secure.

out on releasing START

couple and Multifunctional

button during initial

Control not secure.

light-up, or after
normal operation.

ii.

Faulty power unit on

Replace Multifunctional Control.

Multifunctional Control.

iii.

Faulty thermocouple.

Replace Thermocouple.

c. Main burner lights

i.

No voltage to fan.

Check connections from electrical panel to fan.

but fan fails to run
after approx. 3 min.

ii.

Loose electrical connection

Check connections.

Fan Delay Control.

iii.

Fan Delay Control set incorrectly.

Check for correct settings.

iv.

Faulty fan assembly.

Replace, taking care not to damage
impeller.

v.

Faulty Fan Delay Control.

Replace.

d. Main burner opera-

i.

Gas rate or burner pressure

Check gas rate and burner pressure

ting intermittently

setting high.

setting.

with fan running.

ii.

Temperature rise excessive.

Adjust fan speed or gas rate accordingly.

iii.

Air filter or return air path

Check filter is clean and air path is clear.

restricted.

iv.

Excessive number of outlets

Open additional outlets.

closed.

v.

Spillage of flue gases.

Carry out spillage test and rectify.

vi.

Spillage monitor device (TTB)

Replace Spillage device (TTB)

faulty.

e. Main burner opera-

i.

Gas rate or burner pressure

Check gas rate and burner pressure

ting with intermittent

setting too low.

setting.

fan operation.

ii.

Fan Delay Control set incorrectly.

Check for correct settings.

f. Fan runs for excessive

i.

Fan Delay Control set incorrectly.

Check for correct settings.

period or operates
intermittently after
main burner shuts down.

g. Noisy operation.

i.

Gas pressure too high.

Check burner pressure setting.

ii.

Noisy fan motor.

Replace fan assembly.

iii.

Fan speed setting too high.

Adjust fan speed.

h. Pilot alight but main

i.

Mains electrical supply not

Check mains supply.

burner not igniting.

connected to heater.

ii.

Controls not demanding heat

Check that time control and room thermostat
are operating correctly.

iii.

3A fuse failed.

Replace. If failure occurs again, check
wiring for short circuits.

iv.

Loose connection to room thermo-

Check connections.

stat, Limit Switch, Multifunctional
Control lead, Time Control, or
transformer.

v.

Transformer open circuit.

Check with test meter and replace electrical
assembly.

vi.

Multifunctional Control faulty.

Replace Multifunctional Control.

vii.

Limit Switch faulty.

Short circuit switch, and replace if necessary.

ix.

Room Thermostat or external

Fit temporary loop in heater Thermostat

wiring faulty.

socket. If heater ignites, external circuit

or room thermostat is faulty.

5.2.2

Room Thermostat and its location.

a.

The Room Thermostat should be located where there is free air circulation approx. 1.5m (5ft) from the floor.

b.

Avoid the following locations:

i)

In a room where temperature is greatly affected by the sun or any other heat source, e.g. radiant fire,
wall light fittings or TV set.

ii)

Near an outside door or windows, or on an outside wall.

iii)

Where affected by warm air ducts, diffusers, waste pipes or the heater itself.

iv)

Where subject to vibration.

c.

Connect room thermostat wires control panel terminals ‘16’ and ‘17’

5.3

GAS (SEE BS 5864 AND BS 5482)

5.3.1

An independent gas supply pipe from the meter is to be preferred wherever possible. When this is not possible, the
pipe must be capable of taking the complete input of the heater and all other gas appliances being served by this
same pipe. This supply should be suitably sized to conform to British Standards requirements of no more than 2.5
mbar (1.0 in wg) pressure drop (BS 5482 Pt. 1).

5.3.2

The 

1

/

2

in union gas cock (supplied) must be fitted to the gas inlet of the heater for easy isolation during servicing.

The gas pipe should be so fitted and installed as to be durable, substantial and gas tight. To assist in determining
whether a gas connection may not be tight, a leak detection fluid should be applied around the connection. Under no
circumstances should a flame be used to locate a gas leak.  Gas entry to the air heater is through either side to a Rc

1

/

2

(

1

/

2

in BSP. external [taper] thread).

5.4

DRAUGHT DIVERTER & DEFLECTOR PLATE:

5.4.1

The HI-SPEC J50P heater is supplied with a draught diverter which  houses the TTB, and which requires fitting to the
rear of the heater prior to installation, using 6 x 4mm screws and lock washers (provided). Connect the TTB to the
terminal block situated on the rear upper left hand corner of the appliance.

5.4.2

The deflector plate prevents spillage from the draught diverter in the event of a leak between the air heater and the
base plemum and MUST be fitted as shown in fig 3 using the screws provided.

5.5

DEFLECTOR PLATE SAFETY CHECK:

In order to ensure that the deflector plate is preventing warm air from entering the draught diverter and therefore causing spillage,
the following test MUST be carried out BEFORE commissioning:

5.5.1

Turn on the power supply to the heater.

5.5.2

Set the summer airflow switch to “on”.

5.5.3

Using a smoke match, introduce smoke into the heat exchanger at the burner opening.

5.5.4

Ensure that the smoke is drawn into the heat exchanger and not blown back from the burner opening.

5.5.5

If smoke is blown back from the burner opening, check for air leaks between the heater and the base plenum,
paying particular attention to the rear of the heater directly beneath the draught diverter.

6.

COMMISSIONING

6.1

PREPARATION:

6.1.1

Ensure that:

a.

Gas and Electrical supplies are 

OFF

.

b.

Filter, fan and fan compartments are free from obstructions.

c.

All registers or grilles are open and conform to design specifications.

d.

Return, relief and ventilation air installations are adequate.

6.2

SYSTEM BALANCING:

6.2.1

Set the heater electrical supply ON.

6.2.2

Set the SUMMER AIR CIRCULATION switch to ‘

ON

’.

6.2.3

Balance the system to provide the required volume proportions at the warm air outlets.

NOTE: 

If the system includes ceiling diffusers, air velocities through these should be NOT LESS THAN 1.5m/s (300ft/min), except

for very small rooms, (i.e. bathrooms etc.). Outlet faces may require partial blanking in order to achieve this.

6.2.4

Set the SUMMER AIR CIRCULATION switch to ‘

OFF

’.

Summary of Contents for HI-SPEC J50P

Page 1: ...4 739 BOS00105 Overheat limitControl 1 Honeywell L4069C 6 393 412 BOS02237 Multifunctionalcontrol 1 Honeywell V8600D 7 232 903 BOS02061 Sealing ring for item 6 2 8 BOS02397 2 Pilot assembly 1 9 E01 08...

Page 2: ...her insulation is needed 2 9 For Slot Fix applications see instructions packed with the Slot Fix Kit it is important to ensure that the draught diverter relief is maintained on both sides of the appli...

Page 3: ...oundly sealed 5 1 2 The flue should be kept as short and warm as possible 5 1 3 Sufficient support brackets shall be installed to bear the weight of the total flue system 5 1 4 The spigot connection o...

Page 4: ...ssessed in terms of equivalent vertical height details are given in 5 1 11 For air heaters the minimum equivalent vertical height is 1 metre The installer must make a judgement based on his knowledge...

Page 5: ...e 3 contains the appropriate inlet and outlet flue resistances the flue is likely to be satisfactory if its equivalent height exceeds 1m d WorkedCalculationExample A warm air unit with a 100 mm diamet...

Page 6: ...ectified and the test satisfactorily completed 5 2 ELECTRICAL 5 2 1 Mains a The heater is supplied with mains cable PVC sheathed heat resisting to 85o C 3 core Brown Blue Green Yellow 6A 0 75mm2 conne...

Page 7: ...following locations i In a room where temperature is greatly affected by the sun or any other heat source e g radiant fire wall light fittings or TV set ii Near an outside door or windows or on an out...

Page 8: ...TAPPING1 150V TAPPING2 170V TAPPING3 190V TAPPING4 210V TAPPING5 230V 8 9 6 Disconnect 2 x TTB connections 8 9 7 Disconnect the Multifunctional Control connections 8 9 8 Release 4 x 4mm screws securi...

Page 9: ...e Electrical Assembly cable clamp 8 9 5 Disconnect the following a Disconnect 230V connections L N E from Fan Assembly b 230V mains L N and E from connection block terminals 1 and 3 and earth stud res...

Page 10: ...ar introduce a light source into the heat exchanger burner aperture and upper access port and again examine the heat exchanger for signs of cracks or holes particularly around welded joints whilst aga...

Page 11: ...ar introduce a light source into the heat exchanger burner aperture and upper access port and again examine the heat exchanger for signs of cracks or holes particularly around welded joints whilst aga...

Page 12: ...e Electrical Assembly cable clamp 8 9 5 Disconnect the following a Disconnect 230V connections L N E from Fan Assembly b 230V mains L N and E from connection block terminals 1 and 3 and earth stud res...

Page 13: ...TAPPING1 150V TAPPING2 170V TAPPING3 190V TAPPING4 210V TAPPING5 230V 8 9 6 Disconnect 2 x TTB connections 8 9 7 Disconnect the Multifunctional Control connections 8 9 8 Release 4 x 4mm screws securi...

Page 14: ...following locations i In a room where temperature is greatly affected by the sun or any other heat source e g radiant fire wall light fittings or TV set ii Near an outside door or windows or on an out...

Page 15: ...ectified and the test satisfactorily completed 5 2 ELECTRICAL 5 2 1 Mains a The heater is supplied with mains cable PVC sheathed heat resisting to 85o C 3 core Brown Blue Green Yellow 6A 0 75mm2 conne...

Page 16: ...e 3 contains the appropriate inlet and outlet flue resistances the flue is likely to be satisfactory if its equivalent height exceeds 1m d WorkedCalculationExample A warm air unit with a 100 mm diamet...

Page 17: ...ssessed in terms of equivalent vertical height details are given in 5 1 11 For air heaters the minimum equivalent vertical height is 1 metre The installer must make a judgement based on his knowledge...

Page 18: ...oundly sealed 5 1 2 The flue should be kept as short and warm as possible 5 1 3 Sufficient support brackets shall be installed to bear the weight of the total flue system 5 1 4 The spigot connection o...

Page 19: ...her insulation is needed 2 9 For Slot Fix applications see instructions packed with the Slot Fix Kit it is important to ensure that the draught diverter relief is maintained on both sides of the appli...

Page 20: ...4 739 BOS00105 Overheat limitControl 1 Honeywell L4069C 6 393 412 BOS02237 Multifunctionalcontrol 1 Honeywell V8600D 7 232 903 BOS02061 Sealing ring for item 6 2 8 BOS02397 2 Pilot assembly 1 9 E01 08...

Reviews: