background image

Installation shall be in accordance with the current editions of:-

Building Standards (Scotland) (Consolidation) Regulations
Building Regulations
Gas Safety (Installation and Use) Regulations (as amended)
BS7671 Institute of Electrical Engineers (I.E.E.) Wiring Regulations
BS6891 Installation of Low Pressure Gas Pipework of up to 28mm (R1) in domestic premises (2nd family gases).
BS5440 Pt.1 (Flues for Gas Appliances)
BS5440 Pt.2 (Air Supply for Gas Appliances)
BS5864 Installation of Gas Fired Ducted Air Heaters
Model and Local Authority Bye-laws

IMPORTANT: STATUTE LAW DEFINES THAT ALL GAS APPLIANCES MUST BE INSTALLED BY COMPETENT
PERSONS, (i.e. CORGI REGISTERED INSTALLERS) IN ACCORDANCE WITH THE GAS SAFETY (INSTALLATION
AND USE) REGULATIONS (CURRENT EDITION). FAILURE TO COMPLY WITH THESE REGULATIONS MAY LEAD
TO PROSECUTION.

2.

HEATER COMPARTMENT AND CLEARANCES 

(See BS5864)

2.1

IMPORTANT:   

If the heater is to be fitted to an existing base duct (warm air plenum), always ensure that installation is

carried out such that the rear right hand corner of the heater is aligned with the rear right hand corner of the base duct, so
that any overhang or blanking off will be at the front and/or left hand side. In any event, blanking plates must be
mechanically secured and all joints sealed.

2.2

When the heater is fitted into a compartment a minimum clearance from the compartment side walls of 20mm (0.75 in)
and 25mm (1.0 in) from the front must be left. Consideration should also be given to the space required for the removal
and replacement of the filter tray and the entry of the gas and electrical supplies.

2.3

For service access, a minimum of 600mm (24 ins) is required at the front of the heater. Space must also be allowed, in a
compartment installation, to permit the removal of the heater. The clearance between the appliance and the compartment
must be not less than 75mm (3 in). However, if clearances are less than 75mm, the  internal surface of the compartment
must be lined with non-combustible material. The compartment must be of a fixed rigid structure.

2.4

In airing cupboard installations, the part used as the air heater compartment must comply with the relevant sections of BS
5864 and must be completely separated by either a non-combustible partition, or a perforated metal partition with the
perforations not exceeding 13mm (0.5 in).

2.5

The base duct on which the air heater stands must be only placed on a non-combustible floor.

2.6

IMPORTANT:  The red ‘SAFETY’ label supplied with the heater, MUST BE AFFIXED in a prominent position
on the inside of the compartment door.

3.

VENTILATION AND COMBUSTION AIR

3.1

An SE-duct appliance does not require a combustion air vent in the room or internal space in which it is installed. If
the appliance is installed in a compartment, the minimum total free area of the high and low level ventilation air vents
must be as specified in Table 1 (as per BS5440 Pt. 2 Table 1).

Note:

These free areas allow for the operation of the appliance in combination with an ELJAN 4/SE water heater.

VENTILATED

Low level grille

127  cm

2

 (19.7in

2

)

FROM INSIDE
BUILDING

High level grille

127cm

2

 (19.7in

2

)

VENTILATED

Low level grille

63cm

2

 (9.8in

2

)

FROM OUTSIDE
BUILDING

High level grille

63cm

2

 (9.8in

2

)

Table 1: Minimum Effective Areas

3.2

Both vents must communicate with the same room or internal space, or must both be on the same wall to outside air. The
vertical distance between the vents shall be as large as is practicable. The compartment containing the room sealed
appliance MUST be labelled to warn against blockage of vents - referring to BS 5440 Part 2, clause 4.2.4.

2

23

Fig. 8, PRINCIPAL DIMENSIONS (mm)

SIDE VIEW

REAR VIEW

BASE VIEW

FRONT VIEW

TOP VIEW

3

1

187

380

281

1

6

4

3

6

2

52

33

32

4

1

1

4

7

6

1

2

7

374

459

37

32

257

8

1

6

1

0

2

2

3

9

3

7

6

5

6

6

1

1

1

1

1

0

 d

ia

.

1

2

0

 d

ia

.

KNOCKOUTS
FOR WATER 
CONNECTIONS
(BOTH SIDES)

KNOCKOUT FOR
GAS CONNECTION
(BOTH SIDES)

Summary of Contents for HI-SPEC J25SC Series

Page 1: ...PARES HI SPECJ25SC KEY G CNo MFR SNo DESCRIPTION QTY 1 BOS02064SP Fan Assembly 1 2 T193 0145000 FilterAssembly 1 3 378466 BOS02031 Time Control 1 4 381627 1000 0701140 Multifunctional Control 1 5 2329...

Page 2: ...ent must be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material The compartment must be of a fixed rigi...

Page 3: ...he air filter front cover and the air circulation fan 5 1 2 Cut a hole in the chosen side of the fan compartment The knock outs will determine the size and position 5 1 3 Remove and the filter frame r...

Page 4: ...5 4 4 Apply a suitable mastic not provided to the spigot flanges and insert them into their respective apertures and seal them to the face of the SE duct wall 5 4 5 Position the larger rope ring seal...

Page 5: ...door or windows or on an outside wall iii Where affected by warm air ducts diffusers waste pipes or the heater itself iv Where subject to vibration c Connect Thermista stat Room thermostat wires to c...

Page 6: ...MAXIMUM 6 3 11 Ensure that the main burner has now ignited 6 3 12 Test for gas leakage at the supply Multifunctional control Pilot and Main burners using proprietary detection fluid and sealing any le...

Page 7: ...ch OFF the electrical supply to the air heater 6 8 3 Release the securing screw and hinge down the fan chamber door 6 8 4 Disconnect the air circulation fan as follows a System E T models disconnect t...

Page 8: ...s etc Outlet faces may require partial blanking in order to achieve this 6 9 3 Set the SUMMERAIRFLOW switch to O 6 9 4 Ignite the Pilot and Main burners as detailed in sub paras 6 3 4 to 6 3 7 6 9 5 S...

Page 9: ...arry out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6 1 to 6 8 inclusive Replace any sealing gasket or insulation that is damaged before re commi...

Page 10: ...Thermocouple lock nut from the Pilot Burner Assembly and Multifunctional Control and withdraw the Thermocouple taking care to avoid damage to the capillary 8 5 3 Release the Igniter electrode lock nut...

Page 11: ...0 3 Disconnect terminals 21 to 33 from the Electronic module 8 10 4 Release the 2 x screws and nuts securing Electronic module to Electrical assembly and remove module 8 10 5 Refitting or replacement...

Page 12: ...YSTEM E T models a When carrying out any electrical testing a test meter MUST be used since low resistance test devices can cause damage to the Electronics module b Before commencing defect diagnosis...

Page 13: ...YSTEM E T models a When carrying out any electrical testing a test meter MUST be used since low resistance test devices can cause damage to the Electronics module b Before commencing defect diagnosis...

Page 14: ...0 3 Disconnect terminals 21 to 33 from the Electronic module 8 10 4 Release the 2 x screws and nuts securing Electronic module to Electrical assembly and remove module 8 10 5 Refitting or replacement...

Page 15: ...Thermocouple lock nut from the Pilot Burner Assembly and Multifunctional Control and withdraw the Thermocouple taking care to avoid damage to the capillary 8 5 3 Release the Igniter electrode lock nut...

Page 16: ...arry out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6 1 to 6 8 inclusive Replace any sealing gasket or insulation that is damaged before re commi...

Page 17: ...s etc Outlet faces may require partial blanking in order to achieve this 6 9 3 Set the SUMMERAIRFLOW switch to O 6 9 4 Ignite the Pilot and Main burners as detailed in sub paras 6 3 4 to 6 3 7 6 9 5 S...

Page 18: ...ch OFF the electrical supply to the air heater 6 8 3 Release the securing screw and hinge down the fan chamber door 6 8 4 Disconnect the air circulation fan as follows a System E T models disconnect t...

Page 19: ...MAXIMUM 6 3 11 Ensure that the main burner has now ignited 6 3 12 Test for gas leakage at the supply Multifunctional control Pilot and Main burners using proprietary detection fluid and sealing any le...

Page 20: ...door or windows or on an outside wall iii Where affected by warm air ducts diffusers waste pipes or the heater itself iv Where subject to vibration c Connect Thermista stat Room thermostat wires to c...

Page 21: ...5 4 4 Apply a suitable mastic not provided to the spigot flanges and insert them into their respective apertures and seal them to the face of the SE duct wall 5 4 5 Position the larger rope ring seal...

Page 22: ...he air filter front cover and the air circulation fan 5 1 2 Cut a hole in the chosen side of the fan compartment The knock outs will determine the size and position 5 1 3 Remove and the filter frame r...

Page 23: ...ent must be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material The compartment must be of a fixed rigi...

Page 24: ...PARES HI SPECJ25SC KEY G CNo MFR SNo DESCRIPTION QTY 1 BOS02064SP Fan Assembly 1 2 T193 0145000 FilterAssembly 1 3 378466 BOS02031 Time Control 1 4 381627 1000 0701140 Multifunctional Control 1 5 2329...

Reviews: