FAN OPERATES, BUT BURNER CYCLES BEFORE REQUIRED TEMPERATURE IS REACHED

DOES

THE BURNER

CONTINUE TO

CYCLE?

REPLACE

THERMISTA-STAT

N

CHECK RETURN AIR PATH

FOR RESTRICTIONS

Y

CHECK TEMPERATURE RISE.

IF LESS THAN 60

O

C, LINK

TERMINALS ‘13’ & ‘14’

Y

DOES

THE BURNER

CONTINUE TO

CYCLE?

DOES

THE BURNER

CONTINUE TO

CYCLE?

Y

N

REPLACE FAN DELAY/

LIMIT CONTROL

REPLACE

ELECTRONIC

MODULE

DISCONNECT THERMISTA-STAT

AT TERMINALS ‘7’ & ‘8’, LINK

TERMINALS ‘7’ & ‘TEST’

DO NOT LINK ‘7’ &’8’

7.

INSTRUCTIONS FOR USERS

7.1

If the building is unoccupied, ensure that the Instructions for User are left taped to the air heater for the User, and
Installation Instructions are left at or near the air heater for use on future service calls.

7.2

If the building is occupied, hand the User Instructions over and ensure the User understands:

7.2.1

How to ignite the pilot and burner.

7.2.2

How to operate the Thermista-stat/room thermostat, time and heater ON/OFF switch and summer air circulation

switch, and that the time control must be reset following a power failure.

7.2.3

How to extinguish the pilot and main burner at the Multifunctional control, and switch off electrical supply to the

heater.

7.2.4

How to remove, clean and refit the air filter and at what intervals (i.e. fortnightly, or for new houses, weekly).

7.2.5

How to control the heating system by opening and closing warm air outlets.

7.2.6

How to obtain summer air circulation.

7.2.7

That the air grilles on the heater or heater compartment; grilles and ventilators in the walls, windows or doors of

the building must not be obstructed.

7.2.8

That the heater must be serviced at least once a year by a competent person to ensure efficient and safe operation.

7.2.9

That the red instructions for safe use have been pointed out and understood.

7.2.10 That expert help must be obtained if persistent failure of the pilot burner occurs.

8.

MAINTENANCE

IMPORTANT: Ensure gas and electricity supplies are isolated before commencing any maintenance or
replacement of components. After completion of any maintenance, always test for gas soundness and carry
out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6.1
to 6.8 inclusive. Replace any sealing gasket or insulation that is damaged before re-commissioning, taking
care to not disperse fibrous materials.

8.1

ROUTINE MAINTENANCE:

8.1.1

Operate the appliance and check for the correct function of the burner and controls.

8.1.2

Turn OFF the gas and electrical supplies to the appliance.

8.1.3

Remove the air heater front panel.

8.1.4

Remove and check the return air filter/cleaner for cleanliness, remove and clean the Air Circulation fan as
detailed in para 8.8.

8.1.5

Remove the Burner and Controls Assembly as detailed in para 8.2. Inspect and clean the main burner and injector
as necessary. Examine the main burner for cracks, including hairline cracks, exchanging the burner as necessary.

8.1.6

Inspect and clear the pilot burner orifice.

8.1.7

Clean the heat exchanger flueways by thoroughly brushing from above and below, as shown in para 8.10.

8.1.8

By viewing through the Fan Aperture, and using a torch or similar, examine the heat exchanger externally for signs
of cracks or holes, particularly around welded joints.

8.1.9

Using a torch or similar, introduce a light source into the heat exchanger burner aperture and upper access port,
and again examine the heat exchanger for signs of cracks or holes, particularly around welded joints, whilst again
viewing through the Fan Aperture.

8.1.10 Refit the Air Circulation fan, Burner and Controls Assembly, and air filter/air cleaner.

8.1.11 Light the appliance and note the main burner flame profile. If the flame profile is affected when the Air

Circulation fan switches on, check for any air leaks between the air heater and the base plenum, paying particular
attention to heaters with rear draught diverters. Rectify any air leaks before continuing with this procedure.

8.1.12 Allow the air heater to operate for approximately 15 minutes to ensure stability, and with the main burner lit,

ensure that the operation of Air Circulation fan does not affect the main burner flame profile.

8.1.13 If no defects are found, fully commission the air heater in accordance with the Installation, Commissioning and

Maintenance instructions applicable to the appliance.

Summary of Contents for HI-SPEC J25SC Series

Page 1: ...PARES HI SPECJ25SC KEY G CNo MFR SNo DESCRIPTION QTY 1 BOS02064SP Fan Assembly 1 2 T193 0145000 FilterAssembly 1 3 378466 BOS02031 Time Control 1 4 381627 1000 0701140 Multifunctional Control 1 5 2329...

Page 2: ...ent must be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material The compartment must be of a fixed rigi...

Page 3: ...he air filter front cover and the air circulation fan 5 1 2 Cut a hole in the chosen side of the fan compartment The knock outs will determine the size and position 5 1 3 Remove and the filter frame r...

Page 4: ...5 4 4 Apply a suitable mastic not provided to the spigot flanges and insert them into their respective apertures and seal them to the face of the SE duct wall 5 4 5 Position the larger rope ring seal...

Page 5: ...door or windows or on an outside wall iii Where affected by warm air ducts diffusers waste pipes or the heater itself iv Where subject to vibration c Connect Thermista stat Room thermostat wires to c...

Page 6: ...MAXIMUM 6 3 11 Ensure that the main burner has now ignited 6 3 12 Test for gas leakage at the supply Multifunctional control Pilot and Main burners using proprietary detection fluid and sealing any le...

Page 7: ...ch OFF the electrical supply to the air heater 6 8 3 Release the securing screw and hinge down the fan chamber door 6 8 4 Disconnect the air circulation fan as follows a System E T models disconnect t...

Page 8: ...s etc Outlet faces may require partial blanking in order to achieve this 6 9 3 Set the SUMMERAIRFLOW switch to O 6 9 4 Ignite the Pilot and Main burners as detailed in sub paras 6 3 4 to 6 3 7 6 9 5 S...

Page 9: ...arry out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6 1 to 6 8 inclusive Replace any sealing gasket or insulation that is damaged before re commi...

Page 10: ...Thermocouple lock nut from the Pilot Burner Assembly and Multifunctional Control and withdraw the Thermocouple taking care to avoid damage to the capillary 8 5 3 Release the Igniter electrode lock nut...

Page 11: ...0 3 Disconnect terminals 21 to 33 from the Electronic module 8 10 4 Release the 2 x screws and nuts securing Electronic module to Electrical assembly and remove module 8 10 5 Refitting or replacement...

Page 12: ...YSTEM E T models a When carrying out any electrical testing a test meter MUST be used since low resistance test devices can cause damage to the Electronics module b Before commencing defect diagnosis...

Page 13: ...YSTEM E T models a When carrying out any electrical testing a test meter MUST be used since low resistance test devices can cause damage to the Electronics module b Before commencing defect diagnosis...

Page 14: ...0 3 Disconnect terminals 21 to 33 from the Electronic module 8 10 4 Release the 2 x screws and nuts securing Electronic module to Electrical assembly and remove module 8 10 5 Refitting or replacement...

Page 15: ...Thermocouple lock nut from the Pilot Burner Assembly and Multifunctional Control and withdraw the Thermocouple taking care to avoid damage to the capillary 8 5 3 Release the Igniter electrode lock nut...

Page 16: ...arry out a complete functional test of the appliance in accordance with Commissioning Instructions at Sect 6 1 to 6 8 inclusive Replace any sealing gasket or insulation that is damaged before re commi...

Page 17: ...s etc Outlet faces may require partial blanking in order to achieve this 6 9 3 Set the SUMMERAIRFLOW switch to O 6 9 4 Ignite the Pilot and Main burners as detailed in sub paras 6 3 4 to 6 3 7 6 9 5 S...

Page 18: ...ch OFF the electrical supply to the air heater 6 8 3 Release the securing screw and hinge down the fan chamber door 6 8 4 Disconnect the air circulation fan as follows a System E T models disconnect t...

Page 19: ...MAXIMUM 6 3 11 Ensure that the main burner has now ignited 6 3 12 Test for gas leakage at the supply Multifunctional control Pilot and Main burners using proprietary detection fluid and sealing any le...

Page 20: ...door or windows or on an outside wall iii Where affected by warm air ducts diffusers waste pipes or the heater itself iv Where subject to vibration c Connect Thermista stat Room thermostat wires to c...

Page 21: ...5 4 4 Apply a suitable mastic not provided to the spigot flanges and insert them into their respective apertures and seal them to the face of the SE duct wall 5 4 5 Position the larger rope ring seal...

Page 22: ...he air filter front cover and the air circulation fan 5 1 2 Cut a hole in the chosen side of the fan compartment The knock outs will determine the size and position 5 1 3 Remove and the filter frame r...

Page 23: ...ent must be not less than 75mm 3 in However if clearances are less than 75mm the internal surface of the compartment must be lined with non combustible material The compartment must be of a fixed rigi...

Page 24: ...PARES HI SPECJ25SC KEY G CNo MFR SNo DESCRIPTION QTY 1 BOS02064SP Fan Assembly 1 2 T193 0145000 FilterAssembly 1 3 378466 BOS02031 Time Control 1 4 381627 1000 0701140 Multifunctional Control 1 5 2329...