environment are covered with grids, in units for outdoor use they can be complemented by 
weather-proof blinds. 
 
 

Valves with a small hole designed for connection of air-conditioning piping are, 

as a standard, supplied with an elastic cuff. 
 
 

The  valves  are  supplied  ready  for  fitting  with  actuators  (actuators  may  already  be 

part of the supply) or with manual control. Large valves are split to allow multiple actuators 
to operate. Mixing valves can be coupled with a pull rod for one joint control. 
 

 
Recuperation chamber 

 

The  chamber  for  recovery  of heat from  exhaust  air  may  be  equipped  with  a  rotary 

heat  exchanger  or  plate  heat  exchanger.  The  heat  exchanger  consists  of  a  system  of 
aluminium  plates  (slats)  connected  to  each  other  in  such  a  way  as  to  allow  for  alternate 
passage of the exhaust and supplied air between the plates. In winter period, the exhaust 
air  transfers  heat  to  the  aluminium  plates,  and  they  then  heat  the  supplied  fresh  air.  The 
plate heat exchanger can also  
be used for mixing. 

 
 
Cooling chamber 

 

The  cooling  chamber  is  equipped  with  a  Cu/Al  plate  heat  exchanger,  where  water, 

anti-freezing  mix  or  other  refrigerant  can  be  the  heat  transfer  medium,  according  to  the 
request  of  the  customer.  The  heat  exchanger  is  equipped  with  a  gradient  stainless-steel 
condensate drainage pan and a dropper eliminator. 
 

Burners 

 

As  a  standard,  Weishaupt  pressure  burners  burning  natural  gas,  propane-butane, 

ELFO  (extra  light  fuel  oils)  and  other  types  of  fuel  are  supplied  with  the  unit.  Burners  are 
supplied, as a standard, with two-stage or modulation regulation. Burners include complete 
gas fittings, electrical controls and all safety features. 
 
 

Electrical equipment of the units and MaR 

 

The  units  can  be  supplied  with  control  and  protection  elements  in  any  range 

according to the request of the customer. The units can be supplied, for example, only with 
fitted actuators, can be supplied incl. basic control cabinet only to protect and start up the 
main engines. 
 
 

Regulation  supplied  with  the  unit  is  designed  for  particular  action,  e.g.  in  terms  of 

regulation  requirements  on  room  temperature  (halls)  or  inlet  temperature  (e.g.  paint 
boxes). 
 
 

Unit  control  can  be  manual  (a  combination  of  basic  electrical  control  and  manual 

valve  control),  manually  electronically  from  a  security  cabinet  or  through  advanced 
regulators with a link to other control systems.  

Summary of Contents for MTP

Page 1: ...ENTATION FOR USERS OF AIR HEATERS MTP MTPAL MTP V Contents Page 2 Warranty card 3 Certificate of product quality and completeness Unit test report 5 Technical conditions 11 Installation operating and maintenance instructions 17 Related documents 17 List of warranty and post warranty repair services 18 Optional equipment Warranty card ...

Page 2: ...nty condition commissioning and checking by a qualified worker of an assembly company and completing and signing the Heat exchanger unit commissioning protocol which is an integral part of this warranty card If it is contractually agreed in some cases during the sale the manufacturer reserves commissioning or checking by their own personnel as a warranty condition The warranty can also be contract...

Page 3: ...and ensures their slowdown cooling down the heat exchanger chamber after switching off the unit The amount of air flowing through the heat exchanger chamber has been checked Overall installation quality completeness craftsmanship has been checked For heaters equipped with bypass the following has been checked control of valve actuators in particular the direction of rotation no valve position caus...

Page 4: ... AIR HEATER type design MTP serial number basic tech data Nominal heat input kW Nominal heat output kW Nominal air flow m3 h External air pressure Pa Nominal electrical input kW Weight kg Protection IP Voltage 3x400 V N PE 50 Hz Electric engine used V belt comply with the test regulations date technical control department ___________________________________________________________________________ ...

Page 5: ... type The air is sucked directly from the heated space or via the air conditioning piping The air is heated while circling around the combustion chamber and the tube heat exchanger and being heated it flows through the heater to its discharge section The burners are always pressure burners and only separately certified high quality burners are used The burner is designed according to the fuel used...

Page 6: ...imney outlet usually in the rear wall of the heater the heater with the heat exchanger 525 and higher on the burner wall optionally on another side In most cases the heater is equipped with a bypass which is a separate part in the casing outside the space that is occupied by the heat exchanger and is fitted with a valve A portion of the heated air can then flow through the bypass completely outsid...

Page 7: ... heated air in the heater out of the heat exchanger The specific technical parameters of the supplied heater are always included in this documentation in the Certificate of product quality and completeness and on the nameplate Table of MTP V technical parameters BK maximum heat output standard design minimum air flow standard design kW m3 h P1 45 2400 P2 60 3300 37 50 2700 65 85 4600 100 130 7100 ...

Page 8: ...minal input Weight kW m3 h Pa m3 h kW kg MTP 25 29 2200 40 300 3 11 0 50 1 00 220 MTP 37 45 3000 40 260 4 87 0 50 1 00 220 MTP 50 60 4000 40 340 6 47 0 70 1 50 310 MTP 65 75 5100 40 260 8 06 1 15 1 90 310 MTP 85 100 6600 40 300 10 75 1 15 2 60 450 MTP 100 120 7500 40 280 12 94 1 15 2 60 450 MTP 125 150 10000 40 300 16 13 1 60 3 60 585 MTP 150 175 12000 40 340 18 82 2 70 4 50 590 MTP 175 200 14000 ...

Page 9: ...f product quality and completeness and on the nameplate MTPAL can be equipped with a wide range of accessories such as e g blind shutters filters recuperators cooling exchangers elastic connections etc that do not affect the function of the gas heater Table of MTP technical parameters parameters type 50 80 150 200 300 500 700 900 max output KW 50 80 140 200 275 460 700 900 max flow at 300 Pa 5200 ...

Page 10: ... 2016 426 7 Technical supervision and inspection Technical supervision and inspection during production as well as acceptance are performed by the technical committee of the manufacturer Furthermore the manufacturer reserves participation of their representative in putting the heater into service as the warranty condition 8 Marking On each heater there is a non removable label that contains a manu...

Page 11: ...the wooden prisms or the welded loop If there are two loops on the device it is necessary to use both of them suspension on one loop is not permitted Packaging must not be exposed to direct influences of weather long term exposure to humidity and impacts Storage of heaters must be carried out in well ventilated rooms without the effects of corrosive vapours and aggressive gases or under a shelter ...

Page 12: ...or of flammable material an insulating non conducting pad is used in this case The material used for insulating pads the degree of flammability A B must be resistant to the mechanical effects of the load The dimensions of the pad must be at least the same as the heater floor plan The thickness of the insulating pad must be at least 5 mm No flammable materials can be stored at the location of the h...

Page 13: ...evant project and must comply with the standards for operation of the given type of burner The gas supply and orientation of the burner must be such that the gas inlet does not prevent service access to the tube plate cover For this reason it is advisable to lead the gas supply to the burner in the direction of the air flow If this is not possible it is necessary to allow easy dismantling of the p...

Page 14: ...lectrical connection see drawing No 3 JH 2001C for ESD3J electronic thermostat The heater is equipped with a clamp for protective connection according to ČSN 32 2000 4 41 For the outdoor design of the heater the triple thermostat is provided with a cover Once connected it is necessary to check the direction of speed of the fan engine In case of a triple thermostat it is absolutely necessary to con...

Page 15: ...ermostat T1 this thermostat will disconnect the burner supply The electronic thermostat resets itself when the network is switched on again if the temperature has already dropped below the set value for a long term power outage For a short term power outage it is necessary to wait for the fan to cool the chamber and to reset it by pressing the button on the thermostat T2 operational switches off t...

Page 16: ...as meters X X Check of the location functionality and tightness of regulators X X Check of the location functionality and tightness of gas appliances X X Check of the location of appliances in terms of space ventilation X Visual check of the location and condition of the common space gas pipeline X X Overall visual check of the location and condition of the domestic gas pipeline X Check of the tig...

Page 17: ...f safety thermostat T1 check whether the suction and discharge spaces piping are passable check fan condition loose V belts seized bearings check the filter cloth or also filter inserts if the filters are not clogged it is necessary to consult the defect with the production plant b Flue gases flow into the heated space or higher oxygen content is measured in flue gases check bolt tightening of the...

Page 18: ...rt 1 general requirements Act No 22 1997 Coll as subsequently amended Government Regulation No 22 2003 Coll EU Regulation 2016 426 on Gas Appliances GAR Final protocol No 40 11101 SZU Brno LIST OF WARRANTY AND POST WARRANTY REPAIR SERVICES Warranty and post warranty service of MTP air heaters is provided by our company JINOVA s r o Do Žlábku 733 514 01 Jilemnice tel 481 541 518 481 549 351 e mail ...

Page 19: ...ys with V belts Non standard units are equipped with double fans with a shared shaft or two parallel fans The fan component as a standard includes a door for access to the engine and the fan Upon request it is possible to deliver fan components with eye slits and transmission coverings Filtration component Standard filtration components can be equipped with a whole range of standard cartridge filt...

Page 20: ... chamber is equipped with a Cu Al plate heat exchanger where water anti freezing mix or other refrigerant can be the heat transfer medium according to the request of the customer The heat exchanger is equipped with a gradient stainless steel condensate drainage pan and a dropper eliminator Burners As a standard Weishaupt pressure burners burning natural gas propane butane ELFO extra light fuel oil...

Reviews: