Do Žlábku 733, 514 01 Jilemnice

 

 
Subject: 

MTP Technical documentation 

 

Page No./No. of pages:  

9/20 

 
 

insulation of the unit from sandwich panels filled with mineral wool of thickness of 45 mm. 
Panels are reinforced with glued and riveted profiles for firmness and durability. 
 

Panels  are  attached  into  the  aluminium  frames  according  to  their  position  with 

rivets, bolts and nuts, plastic fasteners or hinges and handles. In addition to standard high-
quality  seals,  the  panels  without  the  need  for  access  regarding  the  outdoor  units  are 
cemented.  Panels  can  be  supplied  powder-coated  in  any  colour  according  to  the  RAL 

sampler at the customerʼs request and for an extra charge.

 

 

All parts of the unit are produced as standard in silicon-free design. 

 

The heaters are supplied in designs for indoor and outdoor use. 

 

The  fan  component  of  the  heaters  is  equipped  with  radial  fans  or  fans  with  a  free 

impeller, with the amount of air and heat output as required by the customer. The engines 
are together with the fans located on an integral frame.  
 

The specific technical parameters of the supplied heater are always included in this 

documentation  in  the  “Certificate  of  product  quality  and  completeness”  and  on  the 

nameplate. 
 

MTPAL can be equipped with a wide range of accessories such as e.g. blind shutters, 

filters,  recuperators,  cooling  exchangers,  elastic  connections  etc.  that  do  not  affect  the 
function of the gas heater. 
 
Table of MTP technical parameters 

parameters/type 

50 

80 

150 

200 

300 

500 

700 

900 

max. output [KW] 

50 

80 

140 

200 

275 

460 

700 

900 

max. flow at 300 Pa 

5200 

8800 

12500 

18000 

25000 

36000 

48000 

60000 

standard engine [KW] 

1.1 - 3 

2.2 - 4 

3 - 5.5 

4 - 7.5 

5.5 - 11 

11 - 18.5 

15 - 30 

22 - 30 

BK 

P1-37 

37-65 

37-100 

37-150 

37-225 

37-400 

37-525 

37-650 

cross section width [mm] 

900 

1100 

1350 

1450 

1600 

2000 

2400 

2800 

cross section height [mm]  700 

900 

1000 

1250 

1500 

1650 

2100 

2200 

 

 

6. Working conditions and conditions for installation 

The  function  of  the  air  heater  can  only  be  guaranteed  if  the  following  working 

conditions are met: 

(a) 

compliance with the following parameters: 

 

- nominal heat input (kW) 

 

- nominal air flow (m

3

/h) 

 

- external resistance must correspond to the proposed value 

 

input  temperature  (for  standard  design  up  to  40  °C,  unless  otherwise 

specified) 

 

- prevention of the chimney effect and return flow 

 

- correct connection of thermostats T1, T2, T3 

b) 

compliance with the environment 

 
The air heaters are made in indoor or outdoor designs. 
 
- the indoor design with IP 40 electrical protection can be used in an ordinary basic 

environment. 

 

Summary of Contents for MTP

Page 1: ...ENTATION FOR USERS OF AIR HEATERS MTP MTPAL MTP V Contents Page 2 Warranty card 3 Certificate of product quality and completeness Unit test report 5 Technical conditions 11 Installation operating and maintenance instructions 17 Related documents 17 List of warranty and post warranty repair services 18 Optional equipment Warranty card ...

Page 2: ...nty condition commissioning and checking by a qualified worker of an assembly company and completing and signing the Heat exchanger unit commissioning protocol which is an integral part of this warranty card If it is contractually agreed in some cases during the sale the manufacturer reserves commissioning or checking by their own personnel as a warranty condition The warranty can also be contract...

Page 3: ...and ensures their slowdown cooling down the heat exchanger chamber after switching off the unit The amount of air flowing through the heat exchanger chamber has been checked Overall installation quality completeness craftsmanship has been checked For heaters equipped with bypass the following has been checked control of valve actuators in particular the direction of rotation no valve position caus...

Page 4: ... AIR HEATER type design MTP serial number basic tech data Nominal heat input kW Nominal heat output kW Nominal air flow m3 h External air pressure Pa Nominal electrical input kW Weight kg Protection IP Voltage 3x400 V N PE 50 Hz Electric engine used V belt comply with the test regulations date technical control department ___________________________________________________________________________ ...

Page 5: ... type The air is sucked directly from the heated space or via the air conditioning piping The air is heated while circling around the combustion chamber and the tube heat exchanger and being heated it flows through the heater to its discharge section The burners are always pressure burners and only separately certified high quality burners are used The burner is designed according to the fuel used...

Page 6: ...imney outlet usually in the rear wall of the heater the heater with the heat exchanger 525 and higher on the burner wall optionally on another side In most cases the heater is equipped with a bypass which is a separate part in the casing outside the space that is occupied by the heat exchanger and is fitted with a valve A portion of the heated air can then flow through the bypass completely outsid...

Page 7: ... heated air in the heater out of the heat exchanger The specific technical parameters of the supplied heater are always included in this documentation in the Certificate of product quality and completeness and on the nameplate Table of MTP V technical parameters BK maximum heat output standard design minimum air flow standard design kW m3 h P1 45 2400 P2 60 3300 37 50 2700 65 85 4600 100 130 7100 ...

Page 8: ...minal input Weight kW m3 h Pa m3 h kW kg MTP 25 29 2200 40 300 3 11 0 50 1 00 220 MTP 37 45 3000 40 260 4 87 0 50 1 00 220 MTP 50 60 4000 40 340 6 47 0 70 1 50 310 MTP 65 75 5100 40 260 8 06 1 15 1 90 310 MTP 85 100 6600 40 300 10 75 1 15 2 60 450 MTP 100 120 7500 40 280 12 94 1 15 2 60 450 MTP 125 150 10000 40 300 16 13 1 60 3 60 585 MTP 150 175 12000 40 340 18 82 2 70 4 50 590 MTP 175 200 14000 ...

Page 9: ...f product quality and completeness and on the nameplate MTPAL can be equipped with a wide range of accessories such as e g blind shutters filters recuperators cooling exchangers elastic connections etc that do not affect the function of the gas heater Table of MTP technical parameters parameters type 50 80 150 200 300 500 700 900 max output KW 50 80 140 200 275 460 700 900 max flow at 300 Pa 5200 ...

Page 10: ... 2016 426 7 Technical supervision and inspection Technical supervision and inspection during production as well as acceptance are performed by the technical committee of the manufacturer Furthermore the manufacturer reserves participation of their representative in putting the heater into service as the warranty condition 8 Marking On each heater there is a non removable label that contains a manu...

Page 11: ...the wooden prisms or the welded loop If there are two loops on the device it is necessary to use both of them suspension on one loop is not permitted Packaging must not be exposed to direct influences of weather long term exposure to humidity and impacts Storage of heaters must be carried out in well ventilated rooms without the effects of corrosive vapours and aggressive gases or under a shelter ...

Page 12: ...or of flammable material an insulating non conducting pad is used in this case The material used for insulating pads the degree of flammability A B must be resistant to the mechanical effects of the load The dimensions of the pad must be at least the same as the heater floor plan The thickness of the insulating pad must be at least 5 mm No flammable materials can be stored at the location of the h...

Page 13: ...evant project and must comply with the standards for operation of the given type of burner The gas supply and orientation of the burner must be such that the gas inlet does not prevent service access to the tube plate cover For this reason it is advisable to lead the gas supply to the burner in the direction of the air flow If this is not possible it is necessary to allow easy dismantling of the p...

Page 14: ...lectrical connection see drawing No 3 JH 2001C for ESD3J electronic thermostat The heater is equipped with a clamp for protective connection according to ČSN 32 2000 4 41 For the outdoor design of the heater the triple thermostat is provided with a cover Once connected it is necessary to check the direction of speed of the fan engine In case of a triple thermostat it is absolutely necessary to con...

Page 15: ...ermostat T1 this thermostat will disconnect the burner supply The electronic thermostat resets itself when the network is switched on again if the temperature has already dropped below the set value for a long term power outage For a short term power outage it is necessary to wait for the fan to cool the chamber and to reset it by pressing the button on the thermostat T2 operational switches off t...

Page 16: ...as meters X X Check of the location functionality and tightness of regulators X X Check of the location functionality and tightness of gas appliances X X Check of the location of appliances in terms of space ventilation X Visual check of the location and condition of the common space gas pipeline X X Overall visual check of the location and condition of the domestic gas pipeline X Check of the tig...

Page 17: ...f safety thermostat T1 check whether the suction and discharge spaces piping are passable check fan condition loose V belts seized bearings check the filter cloth or also filter inserts if the filters are not clogged it is necessary to consult the defect with the production plant b Flue gases flow into the heated space or higher oxygen content is measured in flue gases check bolt tightening of the...

Page 18: ...rt 1 general requirements Act No 22 1997 Coll as subsequently amended Government Regulation No 22 2003 Coll EU Regulation 2016 426 on Gas Appliances GAR Final protocol No 40 11101 SZU Brno LIST OF WARRANTY AND POST WARRANTY REPAIR SERVICES Warranty and post warranty service of MTP air heaters is provided by our company JINOVA s r o Do Žlábku 733 514 01 Jilemnice tel 481 541 518 481 549 351 e mail ...

Page 19: ...ys with V belts Non standard units are equipped with double fans with a shared shaft or two parallel fans The fan component as a standard includes a door for access to the engine and the fan Upon request it is possible to deliver fan components with eye slits and transmission coverings Filtration component Standard filtration components can be equipped with a whole range of standard cartridge filt...

Page 20: ... chamber is equipped with a Cu Al plate heat exchanger where water anti freezing mix or other refrigerant can be the heat transfer medium according to the request of the customer The heat exchanger is equipped with a gradient stainless steel condensate drainage pan and a dropper eliminator Burners As a standard Weishaupt pressure burners burning natural gas propane butane ELFO extra light fuel oil...

Reviews: