Do Žlábku 733, 514 01 Jilemnice

 

 
Subject: 

MTP Technical documentation 

 

Page No./No. of pages:  

8/20 

 
 

The casing is made with sandwich panels with mineral insulation of 30 mm. Surface 

treatment  of panels  is made  of  galvanized  sheet  metal. 

At  customerʼs request,  the heater 

can be supplied in any desired colour according to the RAL sampler.  
 

The  design  for  the  outdoor  environment  is  supplemented  with  a  cover  for  the 

burner,  or  with  a  roof.  Compared  to  the  standard  technical  parameters  stated  below,  the 
parameters  can  be  adjusted  according  to  the  application  requirements  by  using  the 
appropriate engines and by adjusting the amount of air and heat output, always only within 
the  parameters  of  the  corresponding  heat  exchangers  and  MTP-V.  The  specific  technical 
parameters  of  the  supplied  heater  are  always  included  in  this  documentation  in  the 

“Certificate of product quality and completeness” and on the nameplate.

 

 

MTP air heaters can be equipped by the manufacturer with an electrical switchboard 

located on the heater or designed for a stand-alone installation that provides control of the 
burner, engine protection and start up and triple thermostat safety functions. 
Table of MTP technical parameters 

TYPE 

Max. 

heat 

output 

Air flow 

Output 

pressure 

Consumption 

- natural gas 

Nominal input 

Weight 

  

kW 

m

3

/h 

Pa 

m

3

/h 

kW 

kg 

MTP 25 

29 

2200 

40 - 300 

3.11 

0.50 - 1.00 

220 

MTP 37 

45 

3000 

40 - 260 

4.87 

0.50 - 1.00 

220 

MTP 50 

60 

4000 

40 - 340 

6.47 

0.70 - 1.50 

310 

MTP 65 

75 

5100 

40 - 260 

8.06 

1.15 - 1.90 

310 

MTP 85 

100 

6600 

40 - 300 

10.75 

1.15 - 2.60 

450 

MTP 100 

120 

7500 

40 - 280 

12.94 

1.15 - 2.60 

450 

MTP 125 

150 

10000 

40 - 300 

16.13 

1.60 - 3.60 

585 

MTP 150 

175 

12000 

40 - 340 

18.82 

2.70 - 4.50 

590 

MTP 175 

200 

14000 

40 - 360 

21.50 

2.70 - 4.50 

800 

MTP 225 

260 

18000 

40 - 260 

29.97 

4.70 - 6.20 

803 

MTP 300 

350 

24000 

40 - 380 

37.63 

6.50 - 12.00 

1100 

MTP 350 

400 

28000 

40 - 450 

43.00 

8.50 - 16.00 

1120 

MTP 400 

465 

32000 

40 - 280 

49.98 

12.00 - 16.00 

1200 

MTP 525 

600 

41000 

40 - 250 

64.51 

17.00 - 20.50 

2300 

MTP 650 

750 

52000 

40 - 280 

80.64 

17.00 - 24.00 

2800 

MTP 850 

990 

62000 

40 - 300 

106.43 

25.00 - 33.00 

5700 

MTP 1000 

1160 

73500 

40 - 300 

124.74 

25.00 - 33.00 

6000 

 
 

5

 

MTP-AL Specifications: 

MTPAL  air  heaters  are produced  in  block  and  chamber designs.  They  are  produced 

only in a horizontal design on the base frame.  

The  gas  heating  components  are  always  equipped  with  a  ventilation  bypass 

with a valve. The fans are on a common frame with the engine and stored on the vibration 
isolators.  The  units  are  supplemented  by  a  basic  range  of  pocket  filters,  valves,  mixing 
chambers and other common accessories that do not affect the function of the gas heater. 
 

The unit frames are made from modular aluminium profiles of a square cross section 

with  a  side  length  of  50  mm.  The  casing  is  done  with  respect  to  the  maximum  thermal 

Summary of Contents for MTP

Page 1: ...ENTATION FOR USERS OF AIR HEATERS MTP MTPAL MTP V Contents Page 2 Warranty card 3 Certificate of product quality and completeness Unit test report 5 Technical conditions 11 Installation operating and maintenance instructions 17 Related documents 17 List of warranty and post warranty repair services 18 Optional equipment Warranty card ...

Page 2: ...nty condition commissioning and checking by a qualified worker of an assembly company and completing and signing the Heat exchanger unit commissioning protocol which is an integral part of this warranty card If it is contractually agreed in some cases during the sale the manufacturer reserves commissioning or checking by their own personnel as a warranty condition The warranty can also be contract...

Page 3: ...and ensures their slowdown cooling down the heat exchanger chamber after switching off the unit The amount of air flowing through the heat exchanger chamber has been checked Overall installation quality completeness craftsmanship has been checked For heaters equipped with bypass the following has been checked control of valve actuators in particular the direction of rotation no valve position caus...

Page 4: ... AIR HEATER type design MTP serial number basic tech data Nominal heat input kW Nominal heat output kW Nominal air flow m3 h External air pressure Pa Nominal electrical input kW Weight kg Protection IP Voltage 3x400 V N PE 50 Hz Electric engine used V belt comply with the test regulations date technical control department ___________________________________________________________________________ ...

Page 5: ... type The air is sucked directly from the heated space or via the air conditioning piping The air is heated while circling around the combustion chamber and the tube heat exchanger and being heated it flows through the heater to its discharge section The burners are always pressure burners and only separately certified high quality burners are used The burner is designed according to the fuel used...

Page 6: ...imney outlet usually in the rear wall of the heater the heater with the heat exchanger 525 and higher on the burner wall optionally on another side In most cases the heater is equipped with a bypass which is a separate part in the casing outside the space that is occupied by the heat exchanger and is fitted with a valve A portion of the heated air can then flow through the bypass completely outsid...

Page 7: ... heated air in the heater out of the heat exchanger The specific technical parameters of the supplied heater are always included in this documentation in the Certificate of product quality and completeness and on the nameplate Table of MTP V technical parameters BK maximum heat output standard design minimum air flow standard design kW m3 h P1 45 2400 P2 60 3300 37 50 2700 65 85 4600 100 130 7100 ...

Page 8: ...minal input Weight kW m3 h Pa m3 h kW kg MTP 25 29 2200 40 300 3 11 0 50 1 00 220 MTP 37 45 3000 40 260 4 87 0 50 1 00 220 MTP 50 60 4000 40 340 6 47 0 70 1 50 310 MTP 65 75 5100 40 260 8 06 1 15 1 90 310 MTP 85 100 6600 40 300 10 75 1 15 2 60 450 MTP 100 120 7500 40 280 12 94 1 15 2 60 450 MTP 125 150 10000 40 300 16 13 1 60 3 60 585 MTP 150 175 12000 40 340 18 82 2 70 4 50 590 MTP 175 200 14000 ...

Page 9: ...f product quality and completeness and on the nameplate MTPAL can be equipped with a wide range of accessories such as e g blind shutters filters recuperators cooling exchangers elastic connections etc that do not affect the function of the gas heater Table of MTP technical parameters parameters type 50 80 150 200 300 500 700 900 max output KW 50 80 140 200 275 460 700 900 max flow at 300 Pa 5200 ...

Page 10: ... 2016 426 7 Technical supervision and inspection Technical supervision and inspection during production as well as acceptance are performed by the technical committee of the manufacturer Furthermore the manufacturer reserves participation of their representative in putting the heater into service as the warranty condition 8 Marking On each heater there is a non removable label that contains a manu...

Page 11: ...the wooden prisms or the welded loop If there are two loops on the device it is necessary to use both of them suspension on one loop is not permitted Packaging must not be exposed to direct influences of weather long term exposure to humidity and impacts Storage of heaters must be carried out in well ventilated rooms without the effects of corrosive vapours and aggressive gases or under a shelter ...

Page 12: ...or of flammable material an insulating non conducting pad is used in this case The material used for insulating pads the degree of flammability A B must be resistant to the mechanical effects of the load The dimensions of the pad must be at least the same as the heater floor plan The thickness of the insulating pad must be at least 5 mm No flammable materials can be stored at the location of the h...

Page 13: ...evant project and must comply with the standards for operation of the given type of burner The gas supply and orientation of the burner must be such that the gas inlet does not prevent service access to the tube plate cover For this reason it is advisable to lead the gas supply to the burner in the direction of the air flow If this is not possible it is necessary to allow easy dismantling of the p...

Page 14: ...lectrical connection see drawing No 3 JH 2001C for ESD3J electronic thermostat The heater is equipped with a clamp for protective connection according to ČSN 32 2000 4 41 For the outdoor design of the heater the triple thermostat is provided with a cover Once connected it is necessary to check the direction of speed of the fan engine In case of a triple thermostat it is absolutely necessary to con...

Page 15: ...ermostat T1 this thermostat will disconnect the burner supply The electronic thermostat resets itself when the network is switched on again if the temperature has already dropped below the set value for a long term power outage For a short term power outage it is necessary to wait for the fan to cool the chamber and to reset it by pressing the button on the thermostat T2 operational switches off t...

Page 16: ...as meters X X Check of the location functionality and tightness of regulators X X Check of the location functionality and tightness of gas appliances X X Check of the location of appliances in terms of space ventilation X Visual check of the location and condition of the common space gas pipeline X X Overall visual check of the location and condition of the domestic gas pipeline X Check of the tig...

Page 17: ...f safety thermostat T1 check whether the suction and discharge spaces piping are passable check fan condition loose V belts seized bearings check the filter cloth or also filter inserts if the filters are not clogged it is necessary to consult the defect with the production plant b Flue gases flow into the heated space or higher oxygen content is measured in flue gases check bolt tightening of the...

Page 18: ...rt 1 general requirements Act No 22 1997 Coll as subsequently amended Government Regulation No 22 2003 Coll EU Regulation 2016 426 on Gas Appliances GAR Final protocol No 40 11101 SZU Brno LIST OF WARRANTY AND POST WARRANTY REPAIR SERVICES Warranty and post warranty service of MTP air heaters is provided by our company JINOVA s r o Do Žlábku 733 514 01 Jilemnice tel 481 541 518 481 549 351 e mail ...

Page 19: ...ys with V belts Non standard units are equipped with double fans with a shared shaft or two parallel fans The fan component as a standard includes a door for access to the engine and the fan Upon request it is possible to deliver fan components with eye slits and transmission coverings Filtration component Standard filtration components can be equipped with a whole range of standard cartridge filt...

Page 20: ... chamber is equipped with a Cu Al plate heat exchanger where water anti freezing mix or other refrigerant can be the heat transfer medium according to the request of the customer The heat exchanger is equipped with a gradient stainless steel condensate drainage pan and a dropper eliminator Burners As a standard Weishaupt pressure burners burning natural gas propane butane ELFO extra light fuel oil...