d) Check of V-belt tension and wear (as needed). 

 

e) Regular check of input filters (min. once a month) - if the heater is equipped with 
them  or  they  are  in  the  air-conditioning  line  with  the  heater.  When  clogged,  clean 
them  or  replace  the  filter  cloth.  Filter  clogging  time  depends  on  the  intake  air 

pollution. Clogging of the filters significantly reduces the amount of air supplied by 
the heater and increases the temperature of the heat exchanger chamber. The heat 
exchanger may be overheated and thus its service life may be reduced. 

 

f) Lubrication of fan bearings - applies only to some fans, e.g. fans with bearings for 
high temperatures (of ADH-RDH K / K2 type). 
Note:  for  MTP  (MTPAL)  standard  sets,  maintenance-free  bearings  with  permanent 
grease filling are used. 
 

           

 Defects: 

 

 

a) Overheating of heat exchanger, failure of safety thermostat T1 

- check whether the suction and discharge spaces (piping, ...) are passable 
- check fan condition, loose V-belts, seized bearings 

 

- check the filter cloth, or also filter inserts 

 

-  if  the filters  are  not  clogged,  it  is necessary  to  consult the  defect  with  the 

production plant. 

 

b) Flue gases flow into the heated space or higher oxygen content is measured in flue 
gases 

- check bolt tightening of the tube plate cover and the burner flange. 
- replace the seal of the burner flange and the tube plate cover. 
- check whether the combustion chamber is not burned. 

 

LIST OF ACCESSORIES AND SPARE PARTS

 

 
 

Spare  parts are  not  supplied  with the heater.  For  warranty repairs, the  spare parts 

are  available  at  the  production  plant  which  is  authorized  to  carry  out  warranty repairs  on 
the heater (except the burner). 
 

Post-warranty and non-warranty repairs are arranged by the customers themselves, 

the spare parts can be ordered at the production plant. 
 

The warranty does not apply to V-belts and filter cloths.

 

 

This  documentation  provides  the  basis  for  elaboration  of  operating  rules  in 

accordance with ČSN 386405.

 

 
 
 

Summary of Contents for MTP

Page 1: ...ENTATION FOR USERS OF AIR HEATERS MTP MTPAL MTP V Contents Page 2 Warranty card 3 Certificate of product quality and completeness Unit test report 5 Technical conditions 11 Installation operating and maintenance instructions 17 Related documents 17 List of warranty and post warranty repair services 18 Optional equipment Warranty card ...

Page 2: ...nty condition commissioning and checking by a qualified worker of an assembly company and completing and signing the Heat exchanger unit commissioning protocol which is an integral part of this warranty card If it is contractually agreed in some cases during the sale the manufacturer reserves commissioning or checking by their own personnel as a warranty condition The warranty can also be contract...

Page 3: ...and ensures their slowdown cooling down the heat exchanger chamber after switching off the unit The amount of air flowing through the heat exchanger chamber has been checked Overall installation quality completeness craftsmanship has been checked For heaters equipped with bypass the following has been checked control of valve actuators in particular the direction of rotation no valve position caus...

Page 4: ... AIR HEATER type design MTP serial number basic tech data Nominal heat input kW Nominal heat output kW Nominal air flow m3 h External air pressure Pa Nominal electrical input kW Weight kg Protection IP Voltage 3x400 V N PE 50 Hz Electric engine used V belt comply with the test regulations date technical control department ___________________________________________________________________________ ...

Page 5: ... type The air is sucked directly from the heated space or via the air conditioning piping The air is heated while circling around the combustion chamber and the tube heat exchanger and being heated it flows through the heater to its discharge section The burners are always pressure burners and only separately certified high quality burners are used The burner is designed according to the fuel used...

Page 6: ...imney outlet usually in the rear wall of the heater the heater with the heat exchanger 525 and higher on the burner wall optionally on another side In most cases the heater is equipped with a bypass which is a separate part in the casing outside the space that is occupied by the heat exchanger and is fitted with a valve A portion of the heated air can then flow through the bypass completely outsid...

Page 7: ... heated air in the heater out of the heat exchanger The specific technical parameters of the supplied heater are always included in this documentation in the Certificate of product quality and completeness and on the nameplate Table of MTP V technical parameters BK maximum heat output standard design minimum air flow standard design kW m3 h P1 45 2400 P2 60 3300 37 50 2700 65 85 4600 100 130 7100 ...

Page 8: ...minal input Weight kW m3 h Pa m3 h kW kg MTP 25 29 2200 40 300 3 11 0 50 1 00 220 MTP 37 45 3000 40 260 4 87 0 50 1 00 220 MTP 50 60 4000 40 340 6 47 0 70 1 50 310 MTP 65 75 5100 40 260 8 06 1 15 1 90 310 MTP 85 100 6600 40 300 10 75 1 15 2 60 450 MTP 100 120 7500 40 280 12 94 1 15 2 60 450 MTP 125 150 10000 40 300 16 13 1 60 3 60 585 MTP 150 175 12000 40 340 18 82 2 70 4 50 590 MTP 175 200 14000 ...

Page 9: ...f product quality and completeness and on the nameplate MTPAL can be equipped with a wide range of accessories such as e g blind shutters filters recuperators cooling exchangers elastic connections etc that do not affect the function of the gas heater Table of MTP technical parameters parameters type 50 80 150 200 300 500 700 900 max output KW 50 80 140 200 275 460 700 900 max flow at 300 Pa 5200 ...

Page 10: ... 2016 426 7 Technical supervision and inspection Technical supervision and inspection during production as well as acceptance are performed by the technical committee of the manufacturer Furthermore the manufacturer reserves participation of their representative in putting the heater into service as the warranty condition 8 Marking On each heater there is a non removable label that contains a manu...

Page 11: ...the wooden prisms or the welded loop If there are two loops on the device it is necessary to use both of them suspension on one loop is not permitted Packaging must not be exposed to direct influences of weather long term exposure to humidity and impacts Storage of heaters must be carried out in well ventilated rooms without the effects of corrosive vapours and aggressive gases or under a shelter ...

Page 12: ...or of flammable material an insulating non conducting pad is used in this case The material used for insulating pads the degree of flammability A B must be resistant to the mechanical effects of the load The dimensions of the pad must be at least the same as the heater floor plan The thickness of the insulating pad must be at least 5 mm No flammable materials can be stored at the location of the h...

Page 13: ...evant project and must comply with the standards for operation of the given type of burner The gas supply and orientation of the burner must be such that the gas inlet does not prevent service access to the tube plate cover For this reason it is advisable to lead the gas supply to the burner in the direction of the air flow If this is not possible it is necessary to allow easy dismantling of the p...

Page 14: ...lectrical connection see drawing No 3 JH 2001C for ESD3J electronic thermostat The heater is equipped with a clamp for protective connection according to ČSN 32 2000 4 41 For the outdoor design of the heater the triple thermostat is provided with a cover Once connected it is necessary to check the direction of speed of the fan engine In case of a triple thermostat it is absolutely necessary to con...

Page 15: ...ermostat T1 this thermostat will disconnect the burner supply The electronic thermostat resets itself when the network is switched on again if the temperature has already dropped below the set value for a long term power outage For a short term power outage it is necessary to wait for the fan to cool the chamber and to reset it by pressing the button on the thermostat T2 operational switches off t...

Page 16: ...as meters X X Check of the location functionality and tightness of regulators X X Check of the location functionality and tightness of gas appliances X X Check of the location of appliances in terms of space ventilation X Visual check of the location and condition of the common space gas pipeline X X Overall visual check of the location and condition of the domestic gas pipeline X Check of the tig...

Page 17: ...f safety thermostat T1 check whether the suction and discharge spaces piping are passable check fan condition loose V belts seized bearings check the filter cloth or also filter inserts if the filters are not clogged it is necessary to consult the defect with the production plant b Flue gases flow into the heated space or higher oxygen content is measured in flue gases check bolt tightening of the...

Page 18: ...rt 1 general requirements Act No 22 1997 Coll as subsequently amended Government Regulation No 22 2003 Coll EU Regulation 2016 426 on Gas Appliances GAR Final protocol No 40 11101 SZU Brno LIST OF WARRANTY AND POST WARRANTY REPAIR SERVICES Warranty and post warranty service of MTP air heaters is provided by our company JINOVA s r o Do Žlábku 733 514 01 Jilemnice tel 481 541 518 481 549 351 e mail ...

Page 19: ...ys with V belts Non standard units are equipped with double fans with a shared shaft or two parallel fans The fan component as a standard includes a door for access to the engine and the fan Upon request it is possible to deliver fan components with eye slits and transmission coverings Filtration component Standard filtration components can be equipped with a whole range of standard cartridge filt...

Page 20: ... chamber is equipped with a Cu Al plate heat exchanger where water anti freezing mix or other refrigerant can be the heat transfer medium according to the request of the customer The heat exchanger is equipped with a gradient stainless steel condensate drainage pan and a dropper eliminator Burners As a standard Weishaupt pressure burners burning natural gas propane butane ELFO extra light fuel oil...

Reviews: