6 Installation Guide
JetWeb
40
Jetter AG
6.7.2
Description of Connections - Reference
Switch and Strobe Input
Terminal Specifications
• 5-pole terminal block COMBICON RM 5.08 (for printed circuit boards)
• Cable cross-sectional area: 0.25 - 2.5 mm
2
• Torque (for input plug screws): 0,5 .. 0.6 Nm
• The maximum stripping length for input lines is 7 mm.
• The accepted VDE guidelines must be followed
• Bladed screw-driver: 0.6 x 3.5 x 100 mm
Specifications of Connecting Cable
• Not needed
Cable Shielding
Make sure that the signal lines are shielded (see Fig. 6):
• Clamp the shield with the greatest possible surface area under the grounding
clamp and establish an electroconductive connection with the grounding block.
Fig. 10: Connection of strobe sensor and reference switch to X21
Terminal Block X21 - Strobe and Reference Switch
Input
Pin
Signal
Comment
X21.STR
X21.REF
X21.0V
Strobe
pulse
Reference
signal
0 V
Strobe input: DC 24 V,
max. 6 mA
- Low level: up to 2 V
- High level: 20 V ... 30 V
Reference switch:
DC 24 V, max. 6 mA
- Low level: up to 2 V
- High level: 20 V ... 30 V
Reference potential for
both inputs
S 0 V STR 0 V REF
INPUT
X 21
Summary of Contents for JetWeb JX2-CNT1
Page 10: ...Table of Contents JetWeb 10 Jetter AG ...
Page 18: ...1 Safety Instructions JetWeb 18 Jetter AG ...
Page 26: ...JetWeb 26 Jetter AG ...
Page 58: ...8 2 Firmware Version JetWeb 58 Jetter AG ...
Page 60: ...JetWeb 60 Jetter AG ...
Page 74: ...11 1 Reading in SSI data JetWeb 74 Jetter AG Fig 18 Examples Reading in Different SSI Formats ...
Page 82: ...12 1 Sample Program JetWeb 80 Jetter AG ...
Page 90: ...13 2 Mode 2 Operation along with JM 2xx JetWeb 94 Jetter AG ...
Page 91: ...JX2 CNT1 Appendices Jetter AG 95 Appendix ...
Page 92: ...Appendices JetWeb 96 Jetter AG ...
Page 95: ...JX2 CNT1 Appendices Jetter AG 99 ...