18
INSTALLATION
Flue Termination
1 meter
Flue Cowl
500 mm
Flashing
25mm
minimum
Hearth
Packing
Flue Outlet
The Flue Terminal shall be
located so that wind from any
direction is not likely to create
a downdraught in the flue.
A Flue Cowl, AGA Aprroved
to AG604 must be fitted to
the end of the flue pipe. The
minimum flue length must not
be shorter than 3.5 metres.
Maintain a minimum of 500mm
from the bottom of the flue
cowl to the nearest part of
the roof if the flue cowl is at
least 1m from a neighbouring
structure. If less than 1m, the
flue terminal must be located
at least 500mm above that
structure. Refer to AS5601 -
2000 (AG601) sections 5.13.6.2
and 5.13.6.4 to ensure that the
location of the flue terminal
fully complies for installations
with a trafficable roof, a
chimney, another flue terminal
or near any openings into a
building.