16
INSTALLATION
Gas Convector Positioning
1. Position the Gas Convector and Zero Clearance casing at the same height
above the floor as your hearth. (minimum 6mm non-combustible material)
2. Push the Zero Clearance Casing and the Convector Box back into the cutout.
Ensure the power cord is not touching the Zero Clearance housing as shown
right.
3. Ensure air-intakes at bottom of Gas Convector Zero Clearance Casing are not
obstructed.
4. Maintain 25mm clearance from Zero Clearance Casing to combustible
material on back and sides.
Flue Installation
1. This Gas Convector Box must be installed with a minimum of 3 x 1200mm
lengths of flue or more as required (see section referring to clearance above
roof on page 18 of this installation manual).
2. The flue must fit over the spigot as shown in diagram 1, with the corrugated
end of the flue facing upwards. The flue must
NOT
fit inside the spigot, if this
is the case then you have an incorrectly sized flue. The corrugated end of the
flue should
NOT
be fitted as shown in diagram 2, this is
INCORRECT
.
3. Rivet inner flue to collar of gather at three places.
4. Rivet all further inner flues at three places.
5. Using double skin flues space inner and outer flues using 3 x 25mm self
tapping screws through outer casing at bottom, at each join and at top. Also
ensure that flues are ventilated at top and bottom, and when using a cover
cone drill a series of holes into the outer flue below the cover cone to ensure
adequate ventilation.
diagram 1
diagram 2