4.6 Start Submenu for Kerostart.
At the “Start” submenu you first get to this screen
Pressing the “menu up” button will get you to
“Pump Pw. Ignt. K “.
This is the only adjust you have in Kerostart mode
but it is most critical.
A too low value will probably get the fuel ignited
but it will not raise the temperature enough to
trigger the preheat mode, so if you hear or see
flames inside
the turbine but you still get “Ignition
fail” alarm, increase this value one point at a time
until it creates a sufficient temperature change to
pass to next step.
In the last screen you can select the starting
mode “Gas-Star”, ”Kerostart” or “Manual”.