Compact electric control panel is used on the steam generator.
✓
All the control elements on the steam generator are connected to the electric control panel.
✓
The process to be performed on-site on the electrical control panel is to connect the mains
electricity (380V, 50Hz) to the R, S, T and neutral terminals left in the panel.
✓
When connecting the mains to the electrical control panel, use cables of appropriate cross-
section. The total power requirement can be found in the electrical connection section of the
metal label on the steam generator.
✓
In addition to the R, S, T, and neutral terminals, an external ground terminal is also provided in
the electrical control panel. Electrical control panel and external grounding of the device are
made by our factory. All the user has to do is enter the external grounding at the specified point
on the electrical control panel.
✓
The electrical connection you make must be at the required voltage to eliminate possible
disruptions. (380V, 50Hz)
13
f
–
Electricity Connection
ATTENTION!!! Do not interfere with the
electrical control panel in any way and do not
take external energy for any device operating
with electrical energy. The features of the
parts used in the control panel are determined
and
designed
considering
the
power
requirements of the equipment on the steam
generator.
CAUTION!!! Do not take external
grounding as mains neutral. Do not
jump from the neutral terminal to
the external ground terminal. Make
the external grounding as required.