PROBLEM
DESCRIPTION
POSSIBLE REASON
SOLUTION
Fault Nb. 1
High Pressure
Indicates that the specified operation
pressure is exceeded
.
Check whether the safety switch is set to a higher pressure
than the operation switch.
Fault Nb. 2
High Vapor
Temperature
Buhar sıcaklığının set değerinin
üzerine çıktığını gösterir.
The thermostat setpoint, pump flow, condensate tank water
level and pump strainer must be checked. This means that the
system cannot supply enough water and the device has
passed into superheated steam. If the temperature of the
condensate tank water rises above 70, it must be lowered.
Strictly, the first filling must be done manually, after
the water has come out of the first start valve.
Fault Nb. 3
High Smokestack
Temperature
Baca sıcaklığının set değerinin
üzerine çıktığını gösterir.
The thermostat setpoint must be checked. The burner settings
should be reviewed and the capacity reduced if necessary.
First filling must be performed manually after it is seen
that water is coming from the first operation valve.
Fault Nb. 5
Inverter
Malfunction
Indicates the inverter is signaling
an error and no power to the
pump.
See the inverter error codes in the operating instructions
folder.
Fault Nb. 6
Pressurization
Pump Malfunction
Indicates that the thermal of the
pressurization pump inside the
electrical control panel is waste.
Check the electrical voltage to the pressurization pump. Check
the thermal setting.
Fault Nb. 7
Burner Malfunction
Indicates that the burner is not
operating regularly.
It is necessary to check whether the pump pumps the water in
the condensate tank, the amount of water in the condensate
tank, the connections of the water flow controller on the feed
water installation.
Fault Nb. 8
No feed water.
Means no water can be supplied to
the steam generator.
It is necessary to check whether the pump pumps the water in
the condensate tank, the amount of water in the condensate
tank, the connections of the water flow controller on the feed
water installation.
Fault Nb. 0
Speck Pump
Thermic
Malfunction
Indicates that the speck pump
motor thermal inside the electrical
control panel is waste.
Check the electrical voltage to the Speck pump motor. Check
the thermal setting. (2 pumps)