User Manual ECOSTEP®54
39
9
Annex
9.1
Flowcharts for PLC programming
9.1.1
Homing
Flowchart homing for ECO54 axis, initial situation after power-on:
control word = 0x0006, status word = 0x0031.
For safety reasons every movement of an axis should be monitored by the PLC via timeout.
yes
no
no
yes
no
yes
The objects to be written or to be read, resp. for the individual axes are (incl. sub index and length):
Axis 0
Axis 1
Axis 2
Axis 3
control word
60400010
68400010
70400010
78400010
status word
60410010
68410010
70410010
78410010
modes_of_operation
60600008
68600008
70600008
78600008
Set modes_of_operation = 0x06
Start homing and timeout:
control word = 0x001F
Reference found,
status word = 0x9437 ?
control word = 0x000F
Timeout?
Error
status word = 0x8437?
Error
Homing finished successfully!