28
UMG 103
Technical specifications
Ambient conditions during operation
The UMG103 is intended for weather-protected, stationary use. The UMG103
fulfils the use conditions according to DIN IEC 60721-3-3.
Class II according to IEC 60536 (VDE 0106, Part 1), i.e. a PE terminal is not
required!
Transport and storage
The following information applies to devices which are transported or stored in
the original packaging.
Free fall
: 1m
Temperature
: -20°C to +70°C
General information
Net weight
: 150g
Device dimensions
: approx. l=71.5 mm, b=98 mm, h=46mm
Housing flammability class
: UL94V-0
Installed position
: any
Fixing/mounting
: 35 mm top hat rail (according to
IEC/EN 60999-1, DIN EN 50022)
Operating temperature range
: -10°C. +55°C
Relative humidity
: 5 to 95 %, (at +25 °C) without con-
densation
Degree of pollution
: 2
Operating altitude
: 0 .. 2000 m above sea level
Installed position
: any
Ventilation
: Forced ventilation is not required.
Protection against ingress of solid
: IP20 according to EN 60529
foreign bodies and water
September 2000 IEC 60529:1989
Connectable conductors
Solid core, multi-core, flexible core
: 0.08 - 2.5 mm2, AWG 28 - 12
locking torque
: 0.5 Nm max
strip lenght min.
: 8 mm