30
UMG 103
The specifications apply under the following conditions:
- Annual recalibration,
- a warming up time of 10 minutes,
- an ambient temperature of 18 .. 28°C.
If the device is operated outside the range from 18 .. 28°C an additional measurement
error equal to ±0.01% of the measured value must be taken into account per °C
difference.
Measurement uncertainty
The measurement uncertainty of the UMG103 applies to use of the following meas-
uring ranges. The measured value must lie within the given limits. Outside these
limits the measurement uncertainty is unspecified.