33
UMG 103
The UMG103 fulfils the safety requirements of:
Directive 2004/108/EC in conjunction with DIN EN 61326-1 (2006-10) and
Directive 2006/95/EC in conjunction with EN 61010-1 (2002-08)
Safety requirements
Safety requirements for electrical instrumentation, control and laboratory
equipment
: EN 61010-1 08:2002, IEC 61010-1:2001
Protection class
: II (device without protective conductor)
EMC requirements
Emitted interference, residential area
: DIN EN 61326-1:2006, Class A, IEC 61326-2-1:2005
Interference immunity, industrial area
: DIN EN 61326-1:2006, Table 2, IEC 61326-2-1:2005
Housing
: Electrostatic discharge, IEC 61000-4-2 (4 kV/8 kV)
: Electromagnetic fields, IEC 61000-4-3:2002 (10 V/m)
: Electromagnetic fields, IEC 61000-4-8:2000 (100A/m)
Measuring-circuit and power supply voltage
: Voltage dips, IEC 61000-4-11 (0.5 periods)
: Bursts, IEC 61000-4-4 (2 kV)
: Surge voltages, IEC 61000-4-5 (2 kV)
: Conducted HF signals, IEC 61000-4-6 (3 V)
RS485 : Conducted HF signals, IEC 61000-4-6 (3 V)
: Bursts, IEC 61000-4-4 (1 kV)
: Surge voltages, IEC 61000-4-5 (2 kV)
Declaration of conformity