5. Mounting
5.1 Installation location
The device is suitable for installation in stationary
and weather-protected indoor switchboards.
Ground conductive switchboards!
5.2 Mounting orientation
The cut-out dimension in the switchboard is
92
+0.8
mm x 92
+0.8
mm (3.62
+0.03
in x 3.62
+0.03
in).
Minimum clearances for adequate ventilation:
Fig.
Rear view of the mounting orientation of the
UMG 96-PA
5.3 Securing
Secure the device inside the switchboard (mount-
ing plate) with the fastening clips on the side. To
do so, proceed as follows:
·Before inserting the device, remove the fastening
clips (e.g. with a screwdriver) by levering them
horizontally.
Fig.
Side view of UMG 96-PA
with fastening clip.
Mounting plate
Clamping screw
Screwdriver
Fastening
clip
Once the clamping screws touch the mounting plate,
max. 2 further turns to secure the device
·Guide the device through the switchboard
(mounting plate) from the front.
·Attach the clips to the side of the device by
pushing them in and snapping them into place.
·Screw in the clamping screws until they touch
the mounting plate.
·Then tighten the clamping screws with two fur-
ther turns each.
Too tightly tightened clamping
screws can destroy the fastening clips!
ATTENTION
Material damage due to disregard of the instal-
lation instructions!
Disregard of the installation instructions can
damage or destroy your device.
·
Observe the information on the mounting
orientation in the sections “Mounting" and
"Technical Data".
·
Provide adequate air circulation in your
installation environment and, as needed,
cooling when the temperatures are high!
NOTE
UMG 96-PA
MID
:Please note the separate in-
formation about mounting in the chapter