UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
12.4.3 Current and voltage transformers
NOTE
Before configuring the current and voltage trans-
former ratios, be certain to connect the transform-
ers in compliance with the specifications on the
device rating plate and the technical data!
·Open the
Configuration
window as previously
described.
·Use buttons 3 (
) and 4 (
) to select the item
Measurement
and confirm with button 6 (
Enter
).
·The
Measurement
window appears.
·Use buttons 3 (
) and 4 (
) to select the item
Transformer
and confirm with button 6 (
Enter
).
·The
Measurement
window appears with the
settings for the current and voltage transformers
(primary and secondary).
·Use buttons 2 (
), 3 (
), 4 (
) and 5 (
) to
select the entry for the primary or secondary side
Fig.
Measurement window with the item Transformer
activated.
Fig.
Measurement window with the entries for the
transformers
of the transformer to be set and confirm with
button 6 (
Enter
).
·The selected item is shown "yellow".
·Use buttons 2 (
) and 5 (
) to change the
position of the digit to be set for each item and
use buttons 3 (
) and 4 (
) to change the digit
(-1/+1).
·Confirm your entries with button 6 (
Enter
) or end
the action by pressing button 1 (
Esc
).
·To return to the measuring display
Home
, press
button 1 three times (
Esc
) and then press button
2 (
Home
).
Transformer
settings:
·Current transformer (primary):
Setting range:
0 - 10000 A
Default value:
5 A
·Current transformer (secondary):
Setting range:
1 - 5 A
Default value:
5 A
·Voltage transformer (primary):
Setting range:
100 - 60000 V
Default value:
400 V
·Voltage transformer (secondary):
Setting range:
100 - 400 V
Default value:
400 V
·To return to the measuring display
Home
, press
button 1 twice (
Esc
) and then press button 2
(
Home
).
Nominal current
settings:
Setting range:
0 - 999999 A
Default value
:
150 A
NOTE
The
UMG 96-PA-MID/MID+
has an integrated
logbook.
The logbook:
·Appears only in the MID device (see
ization of your load profile can be done using
the GridVis® software. Here, meter readings
of the active energy (applied and delivered) are
offset against previously recorded active en-
ergy measurement data and the difference is
displayed in a registration period (in Germany =
·Records password changes and changes in cur-
rent and voltage transformer ratios (CT and VT).
·Records a maximum of 48 changes with the
recording of the respective meter reading.
After 48 entries in the logbook, the device locks
the configuration of passwords and transformer
ratios. Contact the device manufacturer’s Sup-
port.