www.janitza.de
23
UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
Overcurrent protective device for the line pro-
tection of the supply voltage
Recommendation for the overcurrent protective
device of the supply voltage line protection (de-
pendent on the device variants):
·Option 230 V --> 6 - 16 A (Char. B)
·Option 24 V * --> 1 - 6 A (Char. B)
NOTE
The option "supply voltage of 24 V" is only valid for
the UMG 96-PA (see section
Recommendation for the maximum number of
devices on a line circuit breaker depending on the
variants:
·Option 230 V:
For a B6A line circuit breaker, maximum of 4
devices
For a B16A line circuit breaker, maximum of 11
devices
·Option 24 V:
For a B6A line circuit breaker, maximum of 3
devices
For a B16A line circuit breaker, maximum of 9
devices
NOTE
The fuse is a line protection,
not
a device protec-
tion!
WARNING
Risk of injury due to electrical voltage!
Severe bodily injury or death can result from:
·Touching bare or stripped leads that are ener-
gized.
·Device inputs that pose a hazard when
touched.
Switch off your installation before commenc-
ing work! Secure it against being switched on!
Check to be sure it is de-energized! Ground
and short circuit! Cover or block off adjacent
live parts!
CAUTION
Material damage due to disregard of the con-
nection instructions!
Disregard of the connection instructions can dam-
age or destroy your device.
Therefore please abide by the following:
·
Observe the voltage and frequency specifi-
cations on the rating plate!
·
Connect the supply voltage via a fuse ac-
cording to the technical data!
·
Do not tap the supply voltage from the volt-
age transformers!
·
Provide a fuse for the neutral conductor if
the neutral conductor terminal of the source
is not grounded!
NOTE
Without a functional earth, the device indicates a
residual voltage that is not applied.
N
L
PE/FE
1)
2)
Functional earth
1) Fuse (UL/IEC listed)
2) Isolation device
(disconnect switch or
circuit breaker)
Fig.
"Supply voltage” connection example