UMG 96-PA / UMG 96-PA-MID / UMG 96-PA-MID+
www.janitza.de
76
Fig.
Displays sum (L1..L3) of active, reactive and apparent
energy on the MID device according to software-con-
trolled tariff (not calibrated - ).
14.11 Device acceptance report
When installing and working on
MID devices
, the
person working on the device must ensure that a
device acceptance report is prepared or, if neces-
sary, that entries are supplemented!
The device acceptance report contains informa-
tion on current and voltage transformer types and
their settings (transformer ratios, date and time
specifications).
NOTE
·The device acceptance report must be kept in
a safe, readily available place throughout the
entire service life of the MID devices!
·Create, check and/or complete entries of the
transformer configurations in the device accep-
tance report!
The logbook
·Records password changes and changes in cur-
rent and voltage transformer ratios (CT and VT).
·Records a maximum of 48 changes with the
recording of the respective meter reading.
·Can be reached in the MID window "Active ener-
gy" by pressing button 6.
pr. CT ... primary current transformer
sec. CT ... secondary current transformer
NOTE
The MID devices lock the configuration of pass-
words and transformer ratios after 48 entries in the
logbook.
14.9 Password configuration
Configuration of the MID devices is locked with
a password. You need the password for every
change to the device configuration.
NOTE
·Write down your password and keep it safe!
·You can only configure your device with the
password! If you lose your password, please
inform Janitza Support!
·
The MID devices are configured ex works
with the password 10000.
·
For legal reasons, password protection can-
not be disabled on MID devices.
·If the password is entered incorrectly 4 times,
the device locks the configuration for 15 min-
utes.
Setting range:
00001 - 99999
Default value:
10000
(MID devices)
Information on setting the password can be found
in section „Setting the password“ on page 44
An additional protective measure is to lock the
device for 15 minutes after only three incorrect
entries of the password.
14.10 Tariff measuring display
NOTE
The UMG 96-PA
MID
has software controlled tariffs
which are
not MID-compliant
!
In the
Tariff
display of the MID device, the fol-
lowing symbol appears in case of non-compliant
tariffs: