2. Configuration Files
Local Installation
·Place the USB flash drive with the “config.csv”
file into the USB port of the UMG 804. Note that
the name of the file must not be modified from
“config.csv”
- For F/W versions 1.126 and higher the
UMG 804 will automatically adopt the configu-
ration files after approximately 15 seconds.
- For older firmware, reboot the UMG 804 using
the HTML console “reboot” function under
the “System” tab or remove power to the
UMG 804, wait 10 seconds and then apply
power and the file will be uploaded.
Caution
: do not place the USB with the “config.
csv” file in other UMG 804s unless intentional as
the configuration settings may be automatically
adopted.
config.csv
Reboot Core Module
Remote Installation
(firmware version 1.126 or higher)
Configuration files can be remotely uploaded over
a network.This requires a USB drive to be present
in the UMG 804.
1. Under
Core Module Updates
select “Choose
File” and select the config.csv file to be uploa-
ded.
2. Select “Upload to USB” and wait for the
prompt “File uploaded. Waiting for response.
Success!”
3. The config.csv file is now on the USB drive
in the UMG 804. To upload the file into the
UMG 804 select
“Reboot The Core Module
”
and follow the prompts. Once rebooted the
config files will be uploaded.
Summary of Contents for 14.02.001
Page 7: ...www janitza com UMG 804 7...
Page 30: ...UMG 804 www janitza com 30 8 3 Panel Maps Configuration 8 3 1 Top Feed...
Page 31: ...www janitza com UMG 804 31 PANEL 1 PANEL 2...
Page 32: ...UMG 804 www janitza com 32 8 3 2 Bottom Feed...
Page 33: ...www janitza com UMG 804 33 PANEL 1 PANEL 2...
Page 34: ...UMG 804 www janitza com 34 8 3 3 Single Row Sequential...
Page 35: ...www janitza com UMG 804 35 PANEL 1 PANEL 2...
Page 36: ...UMG 804 www janitza com 36 8 3 4 Single Row Odd Even...
Page 37: ...www janitza com UMG 804 37 PANEL 1 PANEL 2...
Page 42: ...UMG 804 www janitza com 42...
Page 63: ...www janitza com UMG 804 63 14 3 6 Busway Data Currently not available...