UMG 804
www.janitza.com
56
Current Alarm Settings
·Over and under current alarms thresholds are set
separately for
True Meters
and
Virtual Meters
than for individual circuit channels not assigned
a “meter number” which are set on the Detailed
Data page.
·Setting any threshold to “0” will disable the
alarm. It is suggested that the low current
threshold be disabled unless there is a specific
requirement.
·The threshold is a percentage of breaker size
which is set on the “Breaker Size” page under the
“Configuration” tab.
·Alarms can be set for both latching and non-lat-
ching alarm registers.
High Current Alarm threshold; percentage of breaker rating.
High Current Alarm time delay; duration event must be true
before alarm is active.
Low Current Alarm; set at 0 % to disable.
Low Current Alarm time delay; duration event must be true
before alarm.
High Current Non-Latching Alarm; percentage of breaker
rating.
Low Current Non-Latching Alarm; set at 0 % to disable.
Percentage of change required to change alarm state.
Percentage of change required to change alarm state.
Breaker size setting (set on Breaker Size page).
Percent of breaker capacity used.
Measured frequency
Refer also to chapter „Setting Alarm Thresholds“ on
page 58.
Summary of Contents for 14.02.001
Page 7: ...www janitza com UMG 804 7...
Page 30: ...UMG 804 www janitza com 30 8 3 Panel Maps Configuration 8 3 1 Top Feed...
Page 31: ...www janitza com UMG 804 31 PANEL 1 PANEL 2...
Page 32: ...UMG 804 www janitza com 32 8 3 2 Bottom Feed...
Page 33: ...www janitza com UMG 804 33 PANEL 1 PANEL 2...
Page 34: ...UMG 804 www janitza com 34 8 3 3 Single Row Sequential...
Page 35: ...www janitza com UMG 804 35 PANEL 1 PANEL 2...
Page 36: ...UMG 804 www janitza com 36 8 3 4 Single Row Odd Even...
Page 37: ...www janitza com UMG 804 37 PANEL 1 PANEL 2...
Page 42: ...UMG 804 www janitza com 42...
Page 63: ...www janitza com UMG 804 63 14 3 6 Busway Data Currently not available...