Issue: 01.08.2020
Alarm Information
Alarm Settings
The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main sc
and the alarm LED will be on or blinking.
Code
Description
A01
Clock board error
A08
Suction temperature probe fault
A09
Outdoor temperature probe fault
A10
Condensing coil temperature probe fault
A11
Discharge temperature probe fault
A13
Discharge pressure transducer fault
A14
Suction pressure transducer fault
A15
Outside of operating envelope (Digital scroll)
A16
Condensing coil high temperature
A17
Compressor high discharge temperature alarm
A19
Compressor overload trip
A24
Low pressure alarm by transducer
A25
High pressure alarm by transducer
A26
Low pressure alarm by pressure switch
A27
Compressor high pressure alarm by pressure switch
Alarm LED
Off
No alarm
On
Only auto reset alarm
Blinking
Manual reset alarm
Auto:
An alarm condition is created but when cleared the unit will restart automatically.
Manual:
An alarm condition is created but requires resetting manually before the unit can restart.
To Reset Alarm Condition:
•
Press
ALARM
button for more than 5 seconds.
•
Power controller
OFF
then back
ON
.
BACnet and Modbus Protocol
To enable this BACnet and Modbus Protocol feature, an additional serial card
Protocol
Part-code
BACnet MS/TP
PCO10B0BA0
Modbus RTU
PCOS004850
The protocol can be for BACnet protocol or Modbus RTU protocol on screen Fc01
Please contact J & E Hall for the BMS point list for Modbus and BACnet protocol.
The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main sc
Description
Reset type
Auto
Auto
Auto
Condensing coil temperature probe fault
Auto
Auto
Auto
Auto
Outside of operating envelope (Digital scroll)
Auto
Auto
Compressor high discharge temperature alarm
Auto
Auto
Auto:
Auto: less than 3 times in 30 minutes
Manual: 3 times or more in 30 minutes
Low pressure alarm by pressure switch
Auto
Compressor high pressure alarm by pressure switch
Manual
An alarm condition is created but when cleared the unit will restart automatically.
An alarm condition is created but requires resetting manually before the unit can restart.
button for more than 5 seconds.
feature, an additional serial card is required to be plug
Description, (Design Special)
pCOnet BACnet MS/TP RS485 Serial Card
Modbus, Optocoupled RS485 Serial Card
The protocol can be for BACnet protocol or Modbus RTU protocol on screen Fc01
Please contact J & E Hall for the BMS point list for Modbus and BACnet protocol.
Page 30
The alarms below are in ascending order of priority. When there is any alarm, the alarm code will be displayed on the main screen
Reset type
Auto: less than 3 times in 30 minutes
Manual: 3 times or more in 30 minutes
is required to be plugged into the board
Description, (Design Special)
Summary of Contents for JEHSD-0400-B3-M-3
Page 32: ...Issue 01 08 2020 Page 32 Electrical Wiring Diagram JEHSD 0400 B3 M 3 JEHSD 0600 B3 M 3 ...
Page 33: ...Issue 01 08 2020 Page 33 Electrical Wiring Diagram JEHSD 0800 B4 M 3 ...
Page 39: ...Issue 01 08 2020 Page 39 Technical Information Small Version Controller ...
Page 41: ...Issue 01 08 2020 Page 41 Certification ...
Page 42: ...Issue 01 08 2020 Page 42 Certification ...