Issue: 01.08.2020
Commissioning
Altering Low Pressure Alarm Notification Setting
1.
With controller Home screen displayed, Press PRG button to go Main Menu screen and select “
2.
Press ENTER button and followed with
3.
Press ENTER button to move cursor from ‘home’ position to the selection.
notification setting by UP/DOWN arrows.
(i)
Enable alarm msg only (by default)
(ii)
Disable all
(iii)
Enable all
4.
With required low pressure alarm notification setting selected, p
5.
Press ESC button repeatedly to return to Home Screen.
6.
The unit is now ready to run once the cont
The action for each low pressure alarm notification setting
transducer/switch as below:
Low Pressure Alarm Notification
Setting
•
Enable alarm msg only
•
•
•
Disable all
•
•
•
Enable all
•
•
Low Pressure Alarm Notification Setting (Optional)
With controller Home screen displayed, Press PRG button to go Main Menu screen and select “
Press ENTER button and followed with down button till Screen B03 is displayed.
Press ENTER button to move cursor from ‘home’ position to the selection. Select the desired low pressure alarm
notification setting by UP/DOWN arrows. Three type of low pressure alarm notification setting is available:
Enable alarm msg only (by default)
With required low pressure alarm notification setting selected, press ENTER button to confirm.
Press ESC button repeatedly to return to Home Screen.
The unit is now ready to run once the controller is set to ON.
he action for each low pressure alarm notification setting when system pressure is lower than the set limit
Controller Display
Alarm code and warning symbol
are
displayed
Event log is recorded
•
Alarm code and warning symbol
are
not displayed
Event log is recorded
•
Alarm code and warning symbol
are
displayed
Event log is recorded
•
Page 23
With controller Home screen displayed, Press PRG button to go Main Menu screen and select “B.Setpoint”
Select the desired low pressure alarm
Three type of low pressure alarm notification setting is available:
ress ENTER button to confirm.
sure is lower than the set limit of the low pressure
Actions
K4R Alarm relay will not
be activated
K4R Alarm relay will not
be activated
K4R Alarm relay will be
activated after pre-set
time delay (300s)
Summary of Contents for JEHSD-0400-B3-M-3
Page 32: ...Issue 01 08 2020 Page 32 Electrical Wiring Diagram JEHSD 0400 B3 M 3 JEHSD 0600 B3 M 3 ...
Page 33: ...Issue 01 08 2020 Page 33 Electrical Wiring Diagram JEHSD 0800 B4 M 3 ...
Page 39: ...Issue 01 08 2020 Page 39 Technical Information Small Version Controller ...
Page 41: ...Issue 01 08 2020 Page 41 Certification ...
Page 42: ...Issue 01 08 2020 Page 42 Certification ...