Control Logic
Parameters for neutral zone compressor control
1.
Preset differentials for neutral zone, activation
Neutral zone
The operating principle is schematized in the above figure:
Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and
modulation is enabled inside the neutral zone) and the value satisfies the pressure control request in those specific operati
conditions. Therefore within this zone no device is stopped or started.
In the decrease zone, the request also decreases at a rate that depends on the deviation from the set point, and vice
increase zone the request increases proportionally to
For the increase and decrease zones, the following can be used:
• Fixed times: the request decreases or increases constantly as time elapses.
• Variable times: the request decreases or increases more quickly (according to the settings) a
increases.
Note: The figure shows the increase and decrease with fixed times.
Parameters for neutral zone compressor control
Preset differentials for neutral zone, activation zone and deactivation zone.
The operating principle is schematized in the above figure:
Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and
modulation is enabled inside the neutral zone) and the value satisfies the pressure control request in those specific operati
nditions. Therefore within this zone no device is stopped or started.
In the decrease zone, the request also decreases at a rate that depends on the deviation from the set point, and vice
increase zone the request increases proportionally to the deviation.
For the increase and decrease zones, the following can be used:
• Fixed times: the request decreases or increases constantly as time elapses.
• Variable times: the request decreases or increases more quickly (according to the settings) as the deviation from the set point
Note: The figure shows the increase and decrease with fixed times.
Page 27
zone and deactivation zone.
Inside the neutral zone the capacity request sent by the controller is constant (except when there is a modulation device and
modulation is enabled inside the neutral zone) and the value satisfies the pressure control request in those specific operating
In the decrease zone, the request also decreases at a rate that depends on the deviation from the set point, and vice-versa in the
s the deviation from the set point
Summary of Contents for JEHSD-0400-B3-M-3
Page 32: ...Issue 01 08 2020 Page 32 Electrical Wiring Diagram JEHSD 0400 B3 M 3 JEHSD 0600 B3 M 3 ...
Page 33: ...Issue 01 08 2020 Page 33 Electrical Wiring Diagram JEHSD 0800 B4 M 3 ...
Page 39: ...Issue 01 08 2020 Page 39 Technical Information Small Version Controller ...
Page 41: ...Issue 01 08 2020 Page 41 Certification ...
Page 42: ...Issue 01 08 2020 Page 42 Certification ...