curve : Speed versus 0-10V control signal
Min
1
0
10
BMS (V)
Max
4⁰C
1⁰C
1⁰C
2⁰C
Standby mode
Only in combination with a suitable heat
pump and control valve for heating and
cooling
The device automatically enters cooling mode when the water temperature is 2°C/4°F below the
room temperature. If the differential between room and water temperature is less than 1
°
C/2°F, the
device will automatically switch to standby.
The unit starts when the water temperature is < 24°C and the control signal is 1-10V.
The unit is in standby. The unit automatically starts a new cycle if the preset temperature is rea-
ched.
The device automatically enters heating mode when the water
temperature is 4
°
C/7°F above the room temperature. If the
differential between room and water temperature is less than
1
°
C/2°F higher than the room temperature, the device will
automatically switch to standby.
The unit starts if the water temperature is > 28°C/82 ̊F and the
control signal is 1-10V.
Fan speed in function of the incoming control signal.
3. OPERATION