M-P2L1-1 EN
Page 14
Release Date: November 15, 2019
Rev 01
Fitting the batteries
This product shall be used only with the approved battery types shown. Note that the appropriate battery
size depends on whether the optional battery box JBE-BAT has been installed or not:
a) System with primary cabinet only (6.3 mm Faston tab terminals)
•
2x Yuasa NP7-12LFR (7 Ah of C20 capacity)
•
2x Yuasa NP12-12FR (12 Ah of C20 capacity)
b) System with optional battery box (Ø5 mm ring terminals)
•
2x Yuasa NP17-12IFR (17 Ah of C20 capacity)
Use always new batteries in configurations of two (2) identical capacities to provide adequate power for
standby use. Do not mix different battery capacities. Observe the battery manufacturer’s recommendation
on shelf life and expected service life.
Note that batteries pose severe hazards. Read the safety manual of the batteries before handling them.
In order to install the batteries:
1) Remove the screws of the battery holder brackets
Figure 8: Battery Holder Brackets