M-P2L1-1 EN
Page 23
Release Date: November 15, 2019
Rev 01
5.3.
Operations available to all users (access level 1 and above)
This chapter describes the functionality accessible to the building’s first responders, who are considered a
general public user with training and responsibility for initial investigation of incidents related with the fire
system. These functions can be exercised without a password.
Silencing the buzzer
To silence/re-activate the buzzer from the panel in situations as alarm, fault or test, the user can press the
buzzer silence/acknowledge key to silence the buzzer. To re-activate the buzzer, press the same key again
to re-activate the buzzer.
Users can review all previous and ongoing event information from the View menu by pressing either control
keys (refer to Figure 13) or function keys (refer to Figure 14).
View Menu
Under View menu, users will be able to review and go through a variety of historic events, zone and loop
status, along with general system information and date of the last configuration.
To access the View menu, press the Home key and then F1. To return to the previous interface from the
displayed sub-menu, press F6 to exit. The View menu will appear with the following
The sub-menu choices from the Report menu is as follows:
0. View event log
1. View faults
2. View disablements
3. View zone under test
4. View addresses linked to a zone
5. View zone status
6. View device status
7. View addresses used in a loop
8. View address descriptions
9. View system composition and date of last configuration
Once the user is in View menu, the following sub-menus can be accessed, by pressing the corresponding
number in the keypad on the panel.
5.3.2.1 View event log
Press the Home key and then press F1 to enter the View menu, then press 1 to enter this sub-menu. The
following choices will be displayed:
1. All events
2. Alarms
3. Faults
4. Operator actions
5. I/O log
6. Detector analog acquisition
5.3.2.1.1 All events
Press 1 to enter the sub-menu All events. All of the events are displayed chronologically from newest to
oldest.
F1 stands for the number of the output group, press F2 to return to the first page, press F3 to print out the
event log (if the optional printer is attached), press F4 to return to the previous page, press F5 scroll down
to the next page, and press F6 to exit the current interface.