M-P2L1-1 EN
Page 29
Release Date: November 15, 2019
Rev 01
The panel will remain in disabled functional condition as long as there is one disabled device or zone.
5.4.3.8 Set time
Enter the Set time menu to adjust the date and time of the panel by using the numeric and directional
keypads, press F1 to clear the data, F5 to confirm and F6 to exit.
5.4.3.9 View serial numbers and firmware versions
Entering the View serial numbers and firmware versions menu, operators will be able to view the serial
numbers and firmware versions of the display panel, loop card, power card and display key.
Pressing F3 will print the information on the optional printer, F6 will exit.
“Report” menu tree
Under the Report menu, operators can perform and retrieve detailed data related to the system and the field
devices. Operators can also print event log and save configuration or event log to USB from this menu. The
data users can retrieve from the system mainly consist of status and report from field devices signal, loop
state signal and field devices. The Report menu also allows operators to view advanced programming
configured in the control panel.
Operators can access the report menu by pressing the Home key and then F3, to navigate the menu and its
sub-menus, users can use the alphanumeric navigation keypad.
The sub-menu choices from the Report menu is as follows:
1. Print Event Log
2. Save Config or Event log to USB
3. Field device type status
4. Product serial numbers
5. Loop state signal report
6. Field device raw data report
7. Field device state signal value
8. View advanced programming
5.4.4.1 Print event log
The Print event log menu allows the operator to send to the printer selected information. The following filters
are available:
•
All events
•
Alarms
•
Faults
•
Operator actions
•
I/O log