M-P2L1-1 EN
Page 28
Release Date: November 15, 2019
Rev 01
5.4.3.2 Test output group
This menu allows testing the activation of an output group. A test will activate temporarily all the output
devices associated to a group.
After entering user access level 2 password, enter test output group from operate menu. The operator can
select a specific output group (sounder group, fire routing group) from the main sub-menu by entering in a 1
for yes using the directional keys and the numeric keypad. A programmable group or field devices can be
selected by pressing F2 or F3.
5.4.3.3 Keyboard test
To test the status of the keyboard, enter the Keyboard test menu, as you press all the function and
alphanumeric keys from the panel they will be indicated on the display.
To exit the current interface, press long F6 and the test will finish.
5.4.3.4 Indicators test
Enter the Indicators test menu, the system will immediately test the LED indicators, buzzer and all elements
in the LCD screen. This will allow an inspection of the indicator activation.
After running the tests, the panel will return the Operate menu.
5.4.3.5 Disable zone
Use this menu to set zones in and out of the disabled functional condition.
Enter the Disable zone menu, the list of zones available in the system will appear on the left side of the
interface. The column current indicates for each zone if they are currently disabled.
Selecting 1 will disable the corresponding zone. Select 0 to enable the zone again. Note these operations
require confirmation.
Zone disablements will be indicated with the general disabled LED and in the main screen.
Device faults and alarms will not be processed from disabled zones.
5.4.3.6 Disable output group
This menu allows disabling a specific output group. Disabling an output group implies it will not activate
upon reception of alarms and that faults form the associated output devices will not be ignored.
To disable a group, use “1” in the user interface. Groups can be re-enabled by entering 0 (No).
Group disablements will be indicated with the general disabled LED and in the main screen.
If either the SND or the FB groups are disabled, the specific SND/FB condition LEDs will also activate
permanently to indicate the presence of disablements affecting this output group.
5.4.3.7 Disable device
This menu allows disabling the devices mapped to specific loop addresses. To disable a specific device, the
operator shall enter its loop and address number.
Note regarding disablement of points: When all initiating devices in a zone are disabled, the zone becomes
disabled.