3
NOTE 1: MCA (Minimum Circuit Ampacity) = 125% x Largest
Motor +FLA of all other all other loads.
NOTE 2: MOP (Maximum Overcurrent Protective Device) = 225%
x Largest Motor + FLA of all other all other loads.
All electrical ratings provided in this manual are for reference
only. Always refer to the machine data plate to get exact electrical
information for this machine. All electrical work performed on
machines should be done in accordance with applicable local,
state, territorial and national codes. Work should only be performed
by qualified electricians and authorized service agents. A list of
authorized service agencies is located in the back of this manual.
Note that all electrical wiring used in the AVENGER series
of machines must be rated, at a minimum, for 100°C (212°F).
Furthermore, use copper conductors only.
Where applicable, heating element amperage draws have been
adjusted for the assumed input voltage. Jackson assumes
incoming voltages will be either 208 or 230 volts. Some heating
elements used in the machines are rated for other voltages, such
as 240 volts. Always verify the amperage draw of the machine in
operation when sizing circuit protection.
If the dishmachine is equipped with the optional rinse heater,
note the rinse heater may have its own electrical connection and
therefore require a separate service. Amperage loads for motors
and heaters are indicated on the machine data plate.
The electrical configurations of the AVENGER series of machines
are as follows:
Available Electrical Characteristics:
• 115 volt, 60 Hz, single phase ( AVENGER LT-E only)
• 230 volt, 60 Hz, single phase
• 208 volt, 60 Hz, single phase
• 460 volt, 60 Hz, three phase
Available Wash Tank Heaters:
• 1.5KW (standard for AVENGER LT-E only)
• 4KW (standard for AVENGER HT-E)
Available Rinse Tank Heaters:
• 2KW for top tank (standard for AVENGER HT-E)
• 2KW for bottom tank (standard for AVENGER HT-E)
AVENGER HT-E
Electrical Characteristics
ELECTRICAL REQUIREMENTS
SPECIFICATIONS
VOLTS
115
208
230
480
PHASE
1
1
1
3
FREQ
60
60
60
60
WASH
MOTOR
AMPS
13.2A
6.6 A
6.6 A
1.3A
DRAIN
PUMP
1.0A
0.6 A
0.6 A
1.0A
WASH
HEATER
AMPS
13.0A 15.9 A 17.4 A
5.0A
RINSE
HEATER
AMPS
N/A
15.9 A 17.4 A
5.0A
FLA
13.2A 38.4 A 41.4 A 11.3A
MCA
16.5A 41.35 A 44.35 A 11.63A
MOP
30A
50 A
60 A
17.55A
Summary of Contents for AVENGER HT-E
Page 2: ......
Page 35: ...29 CONTROL PANEL PARTS 1 8 3 2 4 5 6 7 ...
Page 41: ...35 115V CONTROL BOX PARTS ITE 2 3 4 5 6 7 8 9 13 14 15 4 4 2 5 6 8 9 7 3 1 1 ...
Page 46: ...40 WASH DRAIN MOTOR ASSEMBLY PARTS 10 11 12 13 1 2 3 4 5 9 8 6 7 ...
Page 54: ...48 RINSE TANK ASSEMBLY PARTS 8 7 6 5 2 3 4 1 ...
Page 58: ...52 SCHEMATICS 115 VOLT ELECTRICAL DIAGRAM ...
Page 59: ...53 SCHEMATICS 208 230 VOLT ELECTRICAL DIAGRAM ...