24
IQ Power HLC Power Supply
& Control Station
5201259 Rev. D
with the power supply. On the Control Station, the data from Sensors connected
to that Sensor Interface will appear as a tab under the HLC and the interface will
automatically be paired with that HLC power supply for CLFB operation.
Sensor Quantity
: The number of sensors found on sensor interface.
Overall Sensor Avg
: The average voltage reported by all sensors on a sensor interface.
Feedback Sensor Avg
: The feedback voltage for use in CLFB control.
This is determined by using Sensors for Feedback, a user adjustable operating
parameter.
Warning Setpoint
: The web voltage level at which sensor interface will set a
“Warning” and illuminate yellow indicator light on interface. The factory default
value is 5 kV, however this value may be user adjusted.
Alarm Setpoint
: The web voltage level at which the sensor interface will set an
“Alarm” and illuminate the red indicator light on the interface. The factory default
value is 20 kV, however this value may be user adjusted.
Web Voltage Sensor 1,2,3…
: The voltage level reported by a given sensor.
Device Version
: The firmware revision in device.
Alarm Test Utility
: Causes an alarm output to aid in checking/troubleshooting alarm
sensing connections.
Device Calibration
:
Displays the time and date of last calibration and allows for
calibration of the power supply and bar. Calibration is used to set the output level
to 100% with the bar at maximum output (maximum output varies with bar length
and operating conditions).
Clean Bar Threshold
: Displays the threshold in output level percent used to set the
clean bar alarm and allows for setting of the clean bar threshold.