11
IQ Power HLC Power Supply
& Control Station
5201259 Rev. D
NOTE
– DO NOT USE standard Ethernet cables with IQ Power systems.
Avoid permanent equipment damage by using only Simco-Ion modular
cables. (Refer to Section 8, Parts & Accessories).
Figure 4. IQ Power Crossover Modular Cable (black)
C.
Connect Control Station
. The Control Station supplies 24 VDC power for the
IQ Power static eliminator power supplies. Use the 7.62 meter [25 foot] (black)
modular cable supplied with HLC. Longer cables (not supplied) are available.
Cables must be IQ Power 8-conductor modular cables with RJ-45 connectors
wired “crossover” (reference color: black, Figure 4).
The modular cable plugs into one of the connectors labeled “POWER &
COMM” on the Control Station and into either “PS COMM 1” connector on
the HLC Power Supply. (see Figure 5)
Route the modular cable clear of moving machine parts and protect it from
abrasion. Secure using nylon wire ties (not supplied). Do not over-tighten wire
tie.
If there is an excess of modular cable, if possible, cut modular cable to length and
re-terminate using an RJ-45 connector installed with the same “polarization” as
connector removed (note rib / wire color code to modular connector).
The IQ Power HLC will report to the Control Station using the Power Supply
Number (address / device number). It will appear on the Control Station as a
single device. If an IQ Power HL Sensor Interface is paired with the HLC, it
will appear as a tab on the device page.
If multiple IQ Power supplies are connected to the Control Station, each power
supply must have a unique Power Supply Number (address / device number).
This is necessary to enable reliable digital communication.