USER MANUAL SPIKA
9.2 PIPELINE LENGTH INCREASE
SPIKA MS 500 is filled with the necessary quantity of R404A for no more than 16.4 ft (5 m) pipeline length. To increase
this length, add 2.82 oz. (80 g) R404A per 16.4 ft (5 m). The maximum pipeline length increase will be 82 ft (25 m).
SPIKA MS 1000 is filled with the necessary quantity of R404A for no more than 16.4ft (5 m) pipelines length. To
increase this length, add 8.5 oz. (240 g) R404A per 16.4 ft (5 m). The maximum pipeline length increase will be 82 ft
(25 m).
9.3 FACTORY SETTINGS
• Head pressure regulator: 10 bar.
• Pressure switch protection: 30 bar.
9.4 ELECTRICAL CONNECTION
Machines are non-cord-connected and the power line has to be connected at the rear of them. All the power requirements
are on the data plate. Always use qualified personnel.
The power supply for the machine and the remote condenser are independent. This means no wiring between them is
necessary.
Follow all applicable local, state and national codes
Image 2 shows how to connect the remote condenser.
Figure 2. Remote condenser connection
ICE MAKING HEAD
REMOTE CONDENSER
LIQUID LINE
SAE FLARE
LIQUID
ODS
LIQUID
SAE FLARE
DISCHARGE
ODS
DISCHARGE
DISCHAR
GE LINE
PIPE SIZE AND FITTINGS
LIQUID
DISCHAR
GE
MS 1000R
MS 500R
LIQUID LINE
5/16’’ COOPER PIPE
1/4’’ COOPER PIPE
HEAD FITTING
3/8’’ SAE FLARE
3/8’’ SAE FLARE
CONDENSER FITTING
5/16’’ ODS
1/4’’ ODS
DISCHARGE LINE
1/2’’ COOPER PIPE
3/8’’ COOPER PIPE
HEAD FITTING
1/2’’ SAE FLARE
3/8’’ SAE FLARE
CONDENSER FITTING
1/2’’ ODS
3/8’’ ODS