background image

24

INSTALLER

The  heater  is  supplied  configured  for  methane  gas 
operation (G20) as indicated on the nameplate, and is 
factory adjusted.
To change the settings, for example, after extraordinary 
maintenance,  after  having  replaced  the  gas  valve,  or 
after having changed the gas type from methane to LPG 
or back, proceed as follows.

The adjustments may only be made by the manufacturer's 
Technical Service.

NOTE: The appliance may be ordered from the 
manufacturer in the LPG version.

Open  the  gas  cock  and  start  the  heater  an  maximum 
power (thermostat set to pos. 7).

methane g20 (20mbar); nominal and minimum 
pressure adjustment.

Checking the supply pressure

-  slacken  off  the  pressure  port  screw  (1),  connect  the 
pressure gauge and check that the mains pressure (1) is 
between 17 and 25 mbar (as shown in the table), then 
remove the pressure gauge and close the port.
-  slacken  off  the  pressure  port  screw  (2),  connect 
the  pressure  gauge  and  check  that  the  nominal  and 
minimum  pressures  (2)  match  the  values  given  in  the 
table.

Nominal pressure adjustment

With the appliance running at maximum power, and the 
thermostat knob turned to pos. 7.
- check that the nominal pressure values match those 
given in the table.
If necessary, adjust with the pressure regulator on the 
gas  valve  (the  screw  has  a  slot  which  is  accessible 
through the hole between the thermostat knob and the 
ignition/control knob).
Turn  the  regulator  screw  CLOCKWISE  to  increase  the 
pressure and COUNTERCLOCKWISE to decrease it.

Minimum pressure adjustment

always set the minimum pressure only after having 
first set the maximum pressure!

With the appliance running at minimum power, and the 
thermostat knob turned to pos. 1.
- check that the minimum pressure values match those 
given in the table.
If necessary, adjust them with he minimum flow rate 
regulator screw on the right side of the gas valve.
Turn the regulator CLOCKWISE to decrease the pressure 
and COUNTERCLOCKWISE to increase it.
Once  the  settings  have  been  made,  seal  both  the 
pressure and minimum flow rate regulators with a drop 
of paint, then disconnect the pressure gauge from the 
pressure port and turn in the screw.

- lPg - butane g30 (29 mbar) and propane g31 (37 
mbar); nominal and minimum pressure adjustment.

Checking the supply pressure

-  slacken  off  the  pressure  port  screw  (1),  connect  the 
pressure  gauge  and  check  that  the  supply  pressure 
is 29 mbar for butane and 37 mbar for propane, then 
remove the gauge and close the port.
If the mains pressure is too low, use the low pressure 
regulator on the main manifold or the regulator on the 
gas canister itself.
Check that the vaporisation capacity of the LPG system 
is adequate.

Nominal pressure adjustment

With the appliance running at maximum power, slacken 
off the pressure port screw (2), connect the pressure 
gauge  and  check  that  the  nominal  pressure  values 
match those given in the table (Injector pressure).
In  LPG  operation,  for  category  3+  only,  the  regulator 
must  be  decommissioned  by  turning  the  regulator 
screw  clockwise  (3  for  model  SC/SV  and  1  for  model 
SE) to a value just below the maximum supply pressure.
Disconnect the pressure gauge and close the port.
If the appliance is set to pure propane, to prevent the 
heat  exchanger  overheating,  you  must  check  that  the 
unit is specified for this type of gas only and not for a 
propane/butane mix or pure butane.

adjustments

MODEL

18
30

BUTANE

nom. / red.

28,8 / 6,0
28,7 / 6,0

PROPANE

nom. / red.

36,8 / 6,8
36,7 / 6,8

mbar
mbar

45

28,6 / 6,0

36,5 / 6,8 mbar

sc/sV

Summary of Contents for Eco SC Series

Page 1: ...SC SV SE Wall gas stoves NATURAL...

Page 2: ...without timer without fan methane SC30TC M0000 SC 45 PIEZO without timer without fan methane SC45TC M0000 SV 18 PIEZO without timer with fan methane SV18TV M0000 SV 30 PIEZO without timer with fan met...

Page 3: ...chnical qualifications Best regards The Manufacturer The convection heater comes with a MANUFACTURER S WARRANTY which runs from the date of certification by your local Technical service see our websit...

Page 4: ...Electrical hookup Gas hookup TECHNICAL SERVICE Preliminary operations Commissioning Malfunctions Check during and after commissioning Changing the gas type Adjustments Routine maintenance Cleaning the...

Page 5: ...quest a new copy from your local Technical Service Certain basic safety rules apply to the use or electrical and fuel gas powered equipment as follows Do not allow children or unsupervised disabled pe...

Page 6: ...er and start stop the fan adjust the room temperature setting and restore operation after a malfunction SE The heat exchanger which is made of die cast aluminium and with fins assures highly efficient...

Page 7: ...thermostat 7 nameplate 8 fan switch ON OFF 9 gas valve 10 room thermostat sensor 11 power plug 12 power fuse 13 tangential fan 14 burner unit 15 heat exchanger 16 tangential fan thermostat 17 control...

Page 8: ...ng Gross weight including packaging CONVECTION HEATER Gross weight including packaging FAN COIL LPG G30 G31 Methane LPG G30 G31 Methane LPG G30 G31 PILOT BURNER Methane LPG G30 G31 Methane LPG G30 G31...

Page 9: ...GENERAL 9 CL LINE CONNECTOR CVT CONDENSER EA IGNITION ELECTRODE F FUSE IMP MANUAL SWITCH L PHASE N NEUTRAL O TIMER RB RESISTANCE TV FAN THERMOSTAT VT TANGENTIAL FAN functional wiring diagram SV...

Page 10: ...l scheme 230V 230V SP I II CF FLAME CONTROLLER CVT TANGENTIAL FAN CONDENSER EA IGNITION ELECTRODE ER DETECTOR ELECTRODE EV GAS SOLENOID VALVE F FUSE FACL DISTURBANCE FILTER ON LINE CONNECTOR HL POWER...

Page 11: ...ENERAL 11 control panel Timer mode Heater off Room thermostat mode 1 IGNITION COMMAND knob 2 PRESSURE REGULATOR SCREW 3 Room thermostat 4 Timer 5 TANGENTIAL FAN SWITCH ON OFF 6 Function selector SC SV...

Page 12: ...GENERAL 12 1 Timer 2 Status indication 3 Room thermostat 4 Function selector Timer mode Heater off Room thermostat mode 5 Power selector min max 6 ON OFF and release button 7 Fan indicator light SE...

Page 13: ...Dia 6 mm wall plugs n 1 Terminal n 1 Concentric pipes n 1 Centring spring n 1 O Ring gasket n 1 Gas cock with unions n 1 Document wallet n 1 User instruction booklet n 1 Installation booklet n 1 Gas a...

Page 14: ...al Standard kit DISCHARGE INTAKE 60 90mm L 900 EXTERNAL terminal Standard kit DISCHARGE INTAKE 60 90mm L 450 INTERNAL mounting Standard kit DISCHARGE INTAKE 70 110mm L 450 EXTERNAL terminal Standard k...

Page 15: ...to operate properly and for maintenance Make sure that the wall to which you are going to mount it is able to support its weight check that the included plugs can bear the appliance s weight in relati...

Page 16: ...for installation against the wall only the intake and flue pipes run through the wall Before starting the installation make sure the diameters total lengths and the terminals of the pipes are match t...

Page 17: ...Cutting must be perpendicular to the pipe axis please handle with care in order not to deform the pipes Insert the outer pipe through the hole then fit the inner pipe into the outer one Insert the flu...

Page 18: ...e flanging on the mounting template Use the included screws IMPORTANT The Special Kit is different from the Standard one the centring spring is missing You don t need it because the pipes are fixed co...

Page 19: ...polarities must be observed blue is NEUTRAL and yellow green is EARTH Strip the earth wire at least 2 cm longer than the other two wires Do not use the gas or water pipes to earth the appliance Ensure...

Page 20: ...et fan timer models Set the fan mode with the fan On Off switch fan models Set the timer mode switch to Manual timer models SC SV model piezoelectric ignition Turn the thermostat knob to 7 maximum set...

Page 21: ...the master switch to OFF and contact Technical Service Once the heater is running set the clock and timer if present for automatic operation by setting the function selector to timer mode refer to the...

Page 22: ...and tightened before you finally tighten it down with a wrench The injector mounts tightly so there is no need for a gasket Main gas burner injector replacement Unscrew the collar 4 3 8 F from the MAI...

Page 23: ...ting mount tightly to each other there is no need for a gasket Check that the value impressed on the injector matches that given in the table Restore the burner unit in reverse order Make the adjustme...

Page 24: ...e thermostat knob turned to pos 1 check that the minimum pressure values match those given in the table If necessary adjust them with he minimum flow rate regulator screw on the right side of the gas...

Page 25: ...the screw Routine maintenance must be run once a year to ensure that the appliance runs safely and efficiently throughout its service life Doing so also reduces consumption and polluting emissions No...

Page 26: ...ombustion Now check the condition of the burner itself Make sure the injector is in good condition if it is not blow compressed air through it to remove any dirt DO NOT use metal tools for cleaning Cl...

Page 27: ...to the frame and restore the electrical connections to prevent malfunctions such as incorrect speeds or short circuits Fuse burnt out If the appliance does not turn on again following a short circuit...

Page 28: ...e the connectors from their plugs replace the board and replace the cables as before Room thermostat sensor To remove and restore the sensor 1 disconnect the faston connectors from their clips release...

Page 29: ...me and extract it install a new unit in reverse order first install the mounts including dampers to the slots then secure it to the frame and restore the electrical connections to prevent malfunctions...

Page 30: ...alibration Safety thermostat manual re arm To remove and restore the thermostat 3 to facilitate access to the thermostat take off the cover 4 by undoing its screws remove the thermostat bracket 1 by u...

Page 31: ...external jacket 1 by lifting it completely off Restoring the jacket Fit it against the edge of the frame slide the front of the jacket onto the front of the frame and push it fully home Hold it in pla...

Page 32: ...ile the heater is running Intake discharge pipes improperly installed Check restore length of pipes tight connection between appliance and pipes Inadequate or fluctuating gas pressure Check adjust gas...

Page 33: ...proper injectors The pilot does not stay on Check switch replace Thermocouple failure Dirty pilot injector Uneven gas pressure Set the proper pressures Room temperature greater than programmed value S...

Page 34: ...fan failure Intake outlet grilles obstructed Switch faulty Appliance not powerful enough for the room Ignition electrode detection unit faulty earthed or badly connected Clean Free Reposition Replace...

Page 35: ...ontrol board faulty Replace High room temperature Adjust the room thermostat Air in gas pipes Bleed Incorrect ignition electrode distance Reset the gap The appliance starts malfunction shutdown Nozzle...

Page 36: ...36 INSTALLER useful information Retailer Name Address Installer Name Address Technical Service Name Address Date Job...

Page 37: ...37 notes notes...

Page 38: ...38 notes...

Page 39: ...39 warranty...

Page 40: ...NOTE The styling dimensions technical specifications equipment and accessories of the product may be subject to change in the interests of improvement 3520010100 Rev 0...

Reviews: