MINI and MIX Series I/O modules/Modbus
version 1.3
www.gc5.pl
Page 39 / 73
3.11.1.3
Bistabile Relay
In this mode only rising edge on digital input change output state. The action of bistable
relay can by executed remotely by changing the state of bit from false to true in COMMAND
register (40020). Outputs can by also overwritten by DIGITAL OUTPUT register (40018 ),
which allows remote control from BMS.
3.11.1.4
Time Relay NO [ms]
In this mode when the output value is false, rising edge on digital input set output to true
value. Every falling edge on digital input starts the counter from the beginning what means
that the output will stay in true value for a time defined in TIME VALUE register (expressed
in milliseconds), counting from the last falling edge of digital input. The action of time relay
can be executed remotely by changing state from false to true in relevant COMMAND
register (40020). Outputs can be also overwritten by module DIGITAL OUTPUT register
(40018), which allows to remote control from BMS.
3.11.1.5
Time Relay NC [ms]
In this mode when the output value is false, falling edge on digital input set output to true
value. Every rising edge on digital input starts the counter from the beginning what means
that the output will stay in true value for a time defined in TIME VALUE register (expressed
in milliseconds), counting from the last rising edge of digital input. The action of time relay
can be executed remotely by changing state from false to true in relevant COMMAND
register (40020). Outputs can be also overwritten by module DIGITAL OUTPUT register
(40018), which allows to remote control from BMS.
3.11.1.6
Time Relay NO [s]
In this mode when the output value is false, rising edge on digital input set output to true
value. Every falling edge on digital input starts the counter from the beginning what means
that the output will stay in true value for a time defined in TIME VALUE register (expressed
in seconds), counting from the last falling edge of digital input. The action of time relay can
be executed remotely by changing state from false to true in relevant COMMAND register
(40020). Outputs can be also overwritten by module DIGITAL OUTPUT register (40018),
which allows to remote control from BMS.
3.11.1.7
Time Relay NC [s]
In this mode when the output value is false, falling edge on digital input set output to true
value. Every rising edge on digital input starts the counter from the beginning what means
that the output will stay in true value for a time defined in TIME VALUE register (expressed
in seconds), counting from the last rising edge of digital input. The action of time relay can
be executed remotely by changing state from false to true in relevant COMMAND register
(40020). Outputs can be also overwritten by module DIGITAL OUTPUT register (40018),
which allows to remote control from BMS.