MINI and MIX Series I/O modules/Modbus
version 1.3
www.gc5.pl
Page 31 / 73
6,7
Hand status of outputs
4
Table 21 AO Hand status bits
Value of Hand
status
Status
Description
0
AUTO
1
HAND CONTROL
Table 22 AO Hand status value
The current value of output in the hand mode determines register 30125 to 30128.
Hand control value of Analog Outputs 1 – 4 (30125 - 20128)
The registers contain a percentage value of manual control for outputs from 1 to 4.