1.13
Protocol selection
Protocol selection is done by sections 4 and 5 of the S3 switch according to table below:
4
5
Protocol
OFF (0)
OFF (0)
Modbus RTU
OFF (0)
ON (1)
Modbus ASCII
ON (1)
OFF (0)
BACnet Master
ON (1)
ON (1)
BACnet Slave
Table 5 Protocol selection
1.14
Restoring the default settings
To restore the default configuration of all registers, follow the steps below:
1.
Turn off power supply
2.
Set section 6 of S3 switch to ON
3.
Turn on power supply, power LED blinking
4.
Switch section 6 of S3 switch to OFF to restore the default settings. To cancel the
reset, turn off the power and switch section 6 of S3 switch to the OFF position.