4.3
Local I/O status and configuration
Universal Inputs
This page allows to enter configuration parameters and show actual value of Universal
Inputs. To open this page please navigate to Local IO tab and choose Universal Inputs from
submenu.
Figure 30 Universal Inputs page of 8U-IP
•
Figure 34 Types of sensors
Universal Input table has the following fields:
•
Sensor type (Read & Write) allows to set different type of sensor.
•
Resolution (Read & Write), resolution measurement 12bits / 16bits (for PT1000 and
Ni1000 sensors please use 16bits).
•
UI Flag (Read Only), status of UI as DI.
•
Disable Voltage Measurement (Read & Write), disable voltage measuring for resistance
measurement only.
•
L.P. Filter Constant (Read & Write),parameter time constant low pass filter in seconds.
Valid values must be between 0 and 60 seconds (default 2s). Setting value 0 will
disable the filter.
•
Resistance (Read Only), in ohms from 0 to 1000k [Ω].