MINI and MIX Series I/O modules/Modbus
version 1.3
www.gc5.pl
Page 27 / 73
6
7
7
8
Table 15 Universal inputs resolution for MIX38 and MIX38-IP
3.3
Digital Inputs Connections
Connection of Digital Input (Dry Contact)
Figure 22 Connection of DI for MIX38 and MIX38-IP
3.4
Digital Inputs MODBUS Registers
State of Digital Inputs (30016)
This 16-bit register contains the status of the Digital Inputs. Short-circuit input to GND sets
the corresponding bit in the register in accordance with the table below:
No of bit in register
No of Digital Input
0
1
1
2
…
…
10
11
11
12
Table 16 Status of DI for MIX38 and MIX38-IP
Counter 1 – 12 (40023, 40024 – 40045, 40046)
The modules have 32-bit counters, one for each Digital Input.
In the register with lower number is stored lower byte of the counter and in the register with
higher number is stored higher byte of the counter.
In the case you would like to change the value of the register you can write any value (called
preset) for pulse counting registers. In the particular case, you can reset the counter by
entering 0. Reset counter is also possible via the registry 40022.