Parameter/display
Value range
Unit
Factory
setting
= Bold
Explanation
Static force in the
opening direction
(basic parameter for
wind load control)
2 – 15
(reduced in case
of
Low Energy)
10 N
6
The forces acting on the closing edge can be changed using
this parameter. The permissibility of the setting is checked
via internal monitoring. If exceeded, the set value is shown
alternating with the active value. Due to system tolerances,
the actual forces on the door panel have to be measured after
the automatic drive teach-in run and adjusted, if necessary, in
order to comply with the local standards and regulations.
Static force in the
closing direction
(basic parameter for
wind load control)
2 – 15
(reduced in case
of
Low Energy)
10 N
6
The forces acting on the closing edge can be changed using
this parameter. The permissibility of the setting is checked
via internal monitoring. If exceeded, the set value is shown
alternating with the active value. Due to system tolerances,
the actual forces on the door panel have to be measured after
the automatic drive teach-in run and adjusted, if necessary, in
order to comply with the local standards and regulations.
Latching action
pulse
0 – 9
0
In addition to the mechanical latching action, there is a
motor-driven latching action available for the automatic mode.
The motor-driven latching action allows you to overcome door
seals or locking devices during the closing. Starting with a
small value, the setting is to be increased in order to prevent
damage to the door.
It must be ensured that the door itself and the arm assembly/
slide channel mounting is suitable for the addional and
permanently introduced forces. In case of doubt, we
recommend to select the smallest possible setting.
Latching action
angle
2 – 10
Degrees
3
The door opening angle is determined by the latching action
angle after which the motor-driven latching action pulse is
effective.
Locking force
0 – 9
0 = off
1 – 9 = on
The locking force will be permanently applied after the
latching action.
This force is to keep the door in the CLOSED position even if
wind pushes against the door.
The locking force can be set between 0 (off) and 9
(maximum).
Push & Go
0 – 1
0 = off
1 = on
Once activated, the door will be automatically opened when
the door is manually moved from the “CLOSED“ position by
an angle of 4° into the direction of “OPEN“.
For this function, the value “hd“ must also be set to 0.
Program
switch type
0 – 4
0
The internal program switch is active.
1
An external program switch with contacts on the connection
board is connected. The connector of the internal program
switch must be unplugged.
2
Not applicable
3
Not applicable
4
Not applicable
Behavior after a
mains reset
0 – 1
0
In case of a power failure or after a shutdown of the drive
drive unit, the program switch will be automatically switched
to the last known position once the mains is switched on.
Important:
The switching on of the mains may also take place
outside business hours and will therefore affect the insurance
requirements.
1
In case of a power failure or after a shutdown of the drive
unit, the program switch will be automatically switched to the
OFF position when the mains is switched on. This function
should be used if the insurance-company approved lock must
be provided.
Internal program
switch
– switch on delay
0 – 1
0
The function of the internal program switch will be applied by the
drive unit immediately after the switching.
1
After the switching of the internal program switch, the function will
be applied with a delay of 10 s. This function is practical if the PGS
is to be repositioned and the person must pass the door through the
standard detectors after the switching. An additional pushbutton
night/bank is not required.