Parameter/display
Value range
Unit
Factory
setting
= Bold
Explanation
Wall suppression BS
60 – 99
99 = deactivated
Degrees
80
Once the set angle has been reached, the input signal of the
safety sensor hinge side will be ignored. The wall suppression
is required if the door opens against an obstacle. The wider
the detection range of the used safety sensor, the larger the
range has to be within which the detection is ignored. To
protect people, we recommend to minimize this range.
If during the opening of the door the wall suppression angle
is exceeded, a fast flashing point will appear on the top left
on the display of the control unit. This display will disappear
when the angle is smaller.
Test
Safety sensor
0 – 6
0
Test off. The safety sensors will not be tested. In combination
with safety sensors according to EN 16005 or DIN 18650,
one of the parameters 1 – 6 must be used. The test level Low
and High active depends on the sensor and must be set on
the sensor to the same value as the drive unit.
1
Test sensor on hinge side - Level High active
2
Test sensor on opposite hinge side - Level High active
3
Test sensor on hinge side & sensor on opposite hinge side -
Level High active
4
Test sensor on hinge side - Level Low active
5
Test sensor on opposite hinge side - Level Low active
6
Test sensor on hinge side & sensor on opposite hinge side -
Level Low active
Pulse by safety
sensor opposite side
hinge
0 – 1
0
The input signal of the safety sensors will be ignored as soon
as the door is closed.
1
With the door closed, the safety sensor can trigger an
opening pulse.
Suppression
safety sensor BS
during initial run
0 – 1
0
The safety sensor on hinge side is not active during the intial
run (will be suppressed).
1
The safety sensor on hinge side is active during the intial run.
Unlocking time
0 – 40
100 ms
1
The unlocking time starts after the pulse. The door will be
opended only after the unlocking time has lapsed. When
set to “0“, the pushing will not be carried out before the
unlocking. Depending on the locking device used and in
combination with the response contact, the process will
change.
Unlocking force
0 – 9
0
The unlocking force determines the force with which the door
is pushed in the "CLOSED" direction prior to the opening.
The time is determined by the unlocking time parameter.
The pushing in the “CLOSED“ direction can be practical in
order to relieve a possibly existing e-opener and to ensure its
opening. The higher the value is set, the higher the load on
the arms mounting. In order to have a long service life of the
system, adjust this force only as high as really required.
PR module test
0 – 1
O
Test off
1
The test of the PR module is carried out every 24 hours, 10
minutes after the mains has been turned on. In case of an
error, no more unlockings will be carried out and therefore
also no more automatic door movements will be started.
SA
FE
T
Y
SE
NS
O
R
U
NLO
CKI
N
G
IS 9100
—
24 ISEO